Rockwell Automation Publication 1503-UM053C-EN-P - March 2015
43
Contactor Drop-out Time Settings
Appendix A
Fuse Rating
Contactor Drop-out Time Setting (ms)
Voltage
Designation
400A
800A
2R
3R
4R
6R
50
9R
50
12R
18R
75
24R
150
32R
240 *
7200
38R
(1)
75
48X
(1)
150
57X
(1)
200
2 x 18R
(1)
50
2 x 24R
(1)
130
2 x 32R
(1)
240 *
2 x 38R
(1)
(1)
2 x 48X
(1)
(1)
2 x 57X
(1)
(1)
10E
15E
20E
25E
30E
40E
50E
8250
65E
50
50
80E
100E
125E
150E
175E
200E
(1) Fuse not suitable for use with contactor.
IMPORTANT
The drop-out time is chosen to be equal to or greater than the intersection of
the rated contactor interrupting current and the fuse melt time curve (except
where noted *).