Table 3 - Mechanical Ratings
Table 4 - Altitude Derating
Figure 3 - Mechanical Dimensions
Temperature
Operating: 0 … 60 °C ambient at the control module
(1)
(1) Ambient temperature is derated at altitudes above 1000 meters (3300 feet). See
Chapter 1
.
Non-Operating: -40… 85 °C
Altitude
-1000 … 5000 meters
Pollution
Pollution level II (as defined by UL 840 and IEC 60664-1)
Humidity
95% non-condensing
Shock (Operational)
15 g peak, 11 ms
Vibration (operational)
10 … 57 Hz, 0.015 inch displacement peak to peak
57 … 150 Hz, 2.5 g acceleration
Altitude
Maximum Operation Ambient at the control
module
(°C)
(1)
(1) Derate by 2°C / 1000 m for high altitude operation.
-1000 … 0
60
1 … 1000
60
1001 … 2000
58
2001 … 3000
56
3001 … 4000
54
4001 … 5000
52