Setup and Commissioning
IntelliVAC Configuration
The IntelliVAC module is configured for a specific application by setting DIP
switches. They are accessed by loosening the two screws on the front of the unit,
and removing the cover by sliding it forward. The switches are found on the front
edge of the IntelliVAC circuit board, see
Figure 17
. There are 16 switches, with
number 1 being at the top closest to the circuit board part number label, see
Table
on page 32
).
Figure 17 - DIP Switch and Connector Locations
A 1503WC-BMC IntelliVAC unit shipped separately from the factory will have
a default configuration per
Table 9 on page 32
.
SHOCK HAZARD:
Hazardous voltage is present inside the module which may
cause personal injury or death. Remove all sources of power from the module
and discharge any connected capacitors before removing the cover.
IMPORTANT
Remove power from the module before removing the cover and before
changing the DIP switch settings. The new DIP switch settings are recognized
only on power-up.
Dip Switches
Status Indicators
Status Relay Outputs
Ground Stud
Supply Power Input
Interface Connections
Fuse