Rockwell Automation Publication 1503-UM053C-EN-P - March 2015
Appendix A
Contactor Drop-out Time Settings
20E
30E
40E
50E
65E
80E
100E
50
50
125E
150E
175E
200E
250E
300E
350E
75
<5000
400E
100
450E
130
500E
240
600E
240*
75
750E
(1)
200
900E
(1)
240*
2 x 250E
(1)
50
2 x 300E
(1)
75
2 x 350E
(1)
75
2 x 400E
(1)
100
2 x 450E
(1)
130
2 x 500E
(1)
240
2 x 600E
(1)
240
2 x 750E
(1)
(1)
2 x 900E
(1)
(1)
(1)
Fuse not suitable for use with contactor
IMPORTANT
The drop-out time is chosen to be equal to or greater than the intersection of
the rated contactor interrupting current and the fuse melt time curve (except
where noted *).
Fuse Rating
Contactor Drop-out Time Setting (ms)
Voltage
Designation
400A
800A