Rockwell Automation Publication 1503-UM053C-EN-P - March 2015
41
Appendix
A
Contactor Drop-out Time Settings
Typical Settings
The contactor drop-out time settings shown in the following table are typical
minimum values used when the power fuses are provided as part of a complete
MV controller from Rockwell Automation. The recommendations are based on
Ferraz-Shawmut power fuses. Other fuse types may require alternate drop-out
time settings.
The IntelliVAC module DIP switches are designed to provide the minimum
drop-out times shown, see
Chapter 4
.
Table 13 - Typical Contactor Drop-Out Time Settings
IMPORTANT
The drop-out time is chosen to be equal to or greater than the intersection of
the rated contactor interrupting current and the fuse melt time curve (except
where noted *).
Fuse Rating
Contactor Drop-out Time Setting (ms)
Voltage
Designation
400A
800A
2R
3R
4R
6R
9R
50
12R
18R
50
19R
<5000
24R
100
32R
240
38R
(1)
48X
(1)
75
57X
(1)
200
2 x 24R
(1)
100
2 x 32R
(1)
240*
2 x 38R
(1)
(1)
2 x 48X
(1)
(1)
2 x 57X
(1)
(1)