30
Rockwell Automation Publication 1503-UM053C-EN-P - March 2015
Chapter 3
Installation and Wiring
Table on page 32
of the “Setup and Commissioning” chapter has the dip switch
settings to provide TDUV from 0.2 …2 seconds. IntelliVAC can provide TDUV
protection without the use of an external capacitor, see
Table 8 on page 30
.
Table 8 - Maximum TDUV Time (
without
Capacitor)
If the undervoltage condition persists beyond the set delay time, the contactor will
be opened and an undervoltage fault or warning condition will occur, see
Chapter 5
.
Figure 16 - TDUV Control Circuit
ATTENTION:
The TDUV feature has limitations, if used for an input contactor on
a PF7000 drive with the Safe Torque Off option. See
Table on page 32
.
Control Voltage
Max. TDUV Time (s)
400 A
800A
110/120V
0.2
0.2
220/240V
1.0
1.0
MOV
3
2
1
EC
-
+
4
TCO
12
11
AUX
CCO
5
6
L1
L2/N
G
+ -
M-IV
9
10
M-IV
15
16
M
M-IV
M
Control Power
Control Power Fuse
*
*
See
Table 5 on page 19
for recommended fuse sizing.
Overload
Stop
Start
Contactor
Status
Close
Capacitor