Chapter 5
Monitoring and Troubleshooting
Table 11 - IntelliVAC Status Indication
(Series D only)
Conditions
(1)
(2)
Description
Module Status
Contactor Status
Status
Indicator Color
Status Relay
Status Indicator
Color
Status Relay
Normal
Healthy Module and Contactor OPEN
Green
Closed
Off
Open
Normal
Healthy Module and Contactor CLOSED
Green
Closed
Yellow
Closed
Warning
Invalid Command Present
(3)
Yellow
Closed
Off
Open
Warning
Mechanical Latch Fail to Trip
Yellow
Closed
Yellow
Closed
Fault
Power Up with Contactor CLOSED
(4)
Red - Flash 2
(6)
Open
Yellow
Closed
Warning
Contactor Fails to Pick Up
Yellow - R1
(7)
Closed
Off / Yellow
(12)
Open / Closed
(12)
Warning
Contactor Drop Out During Hold
Yellow - R2
(8)
Closed
Off / Yellow
(12)
Open / Closed
(12)
Warning
Long Contactor Drop Out Time
Yellow - R3
(9)
Closed
Off / Yellow
(12)
Open / Closed
(12)
Fault
Microcontroller Malfunction
Red
Open
Red
Open
Fault
Power Up with Invalid Dip Switch Configuration
Red - Flash 1
(10)
Open
Off
Open
Warning
Undervoltage with a CLOSE Command Present
(5)
Yellow - Flashing
Open / Closed
(11)
Off / Yellow
(12)
Open / Closed
(12)
(1) Warnings will be cleared when a change of input state occurs, and the condition has been resolved.
(2) Faults require control power to be removed until the unit resets.
(3) Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence.
2. Close or Jog command reapplied too quickly (before contactor opening sequence is verified).
Allow at least 60 msec, plus drop out delay time, before reapplying these signals.
NOTE:
Contactor will only respond to a close command reapplications after the restart delay timer has expired.
3.Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).
(4) Only for Electrically Held Contactor.
(5) Undervoltage conditions are defined on page 3-17.
(6) Flash 2 = 2 Consecutive Red status indicator flashes followed by a pause.
(7) Yellow – R1 = Yellow with 1 Red status indicator flash followed by a pause.
(8) Yellow – R2 = Yellow with 2 consecutive Red status indicator flashes followed by a pause.
(9) Yellow – R3 = Yellow with 3 consecutive Red status indicator flashes followed by a pause.
(10) Flash 1 = 1 Red status indicator flash followed by a pause.
(11) Open during undervoltage, Closed if voltage restored.
(12) Will reflect actual status of the contactor.
Summary of Contents for Allen-Bradley IntelliVAC 1503VC-BMC5
Page 1: ...IntelliVAC Contactor Control Module Catalog Number Bulletin 1503VC Series E User Manual...
Page 6: ...6 Rockwell Automation Publication 1503 UM053C EN P March 2015 Summary of Changes Notes...
Page 40: ...40 Rockwell Automation Publication 1503 UM053C EN P March 2015 Chapter 6 Spare Parts Notes...
Page 45: ......