5-4
Parameters and Programming
Display Group (Read Only)
No.
Parameter Name/Description
Min./Max. Range
Units
12
[Input Status]
Displays the open (0) and closed (1) state of the inputs to TB3 in binary coded
format as follows:
0000/1111
Binary Number
13
[Power Factor Angle]
Displays the angle in electrical degrees between motor voltage and motor current.
0.0/180.0
0.1 degrees
14
[Memory Probe Display]
Used by Rockwell Automation field service personnel.
Numeric Value
Numeric Value
15
[Preset Status]
Displays the open (0) and closed (1)
state of TB3 inputs SW1, SW2 and
SW3 in binary coded format.
Preset –
0000/0111
Analog –
0000/0011
Binary Number
16
[Analog Input]
Displays the analog input as a percent of full scale. Used in setting P60 - [Zero
Offset], P75 - [Analog Input Minimum], and P76 - [Analog Input Maximum].
Important:
On initial set up of the drive, apply a 0V or 4 mA analog command to
the drive. Once applied, if the value of this parameter displays
something other than zero, program that value into P60 - [Zero Offset].
Please note that the value of [Zero Offset] will be subtracted from the
value of this parameter.
–150.0/+150.0
0.1%
Bit 3
Polarity
Bit 2
TB3-6
Bit 1
TB3-8
Bit 0
TB3-5
Input Mode 0
(3-Wire)
0 =
Positive
Analog
Input
1 =
Negative
Analog
Input
Start
Stop
Reverse
Input Mode 1
(2-Wire)
Run
Forward
Stop
Run
Reverse
Input Mode 2
(Keypad)
N/A
Stop
N/A
Input Mode 3
(Mom. Run Fwd./Rev.)
Run
Forward
Stop
Run
Reverse
Input Mode 4
(Accel/Decel)
Run
Forward
0 = Accel 2/Decel 2
1 = Accel 1/Decel 1
Run
Reverse
Input Mode 5
(Coast to Rest)
Run
Forward
Coast to Rest Stop
Run
Reverse
Input Mode 6
(TB3 Control/
Keypad or Comm.)
Run
Forward
0 = TB3 Control
1 = Keypad or Comm.
Run
Reverse
Input Mode 7
(Frequency Select)
Run
Forward
0 = Analog Frequency Select
1 = Internal Frequency Select
Run
Reverse
Input Mode 8
➊
(SF1 Preset Speed)
Run
Forward
0 = Open
1 = Closed
Run
Reverse
Input Mode 9
(2-Wire PI control)
Run
Forward
0 = PI
1 = Internal Frequency Select
Run
Reverse
➊
Status of Bit 3 for Input Mode 8 is TB3-2 is: 0 = Open, 1 = Closed.
SW1
SW2
SW3
Not Used
Bit 3
Bit 2
Bit 1
Bit 0
This parameter applies only to the Analog Signal Follower model.
This TB3 input applies only to the Preset Speed model.
Summary of Contents for Allen-Bradley 160 SSC Series
Page 12: ...1 6 Getting Started End of Chapter ...
Page 58: ...5 20 Parameters and Programming End of Chapter ...
Page 66: ...A 4 Specifications End of Chapter ...
Page 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Page 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Page 82: ...C 6 CE Conformity End of Chapter ...
Page 87: ......