CE Conformity
C-3
Cable Clamps
• Use suitable EMC-tested cable clamps only.
• The connection area must be 360 degrees around the shielded cable.
• The cable clamps also provide strain-relief for the cable.
• When using conduit, the contact point of metal entry connections must be free
of paint or non-conductive surfaces and solidly connected with good
conductivity to the enclosure.
Motor Cable
• The cable between the drive and motor must be a 4-wire shielded cable (three
phases and ground).
• Do not exceed the maximum motor cable length for the specific line filter
module used.
• Inside the shielded enclosure, shielded motor cable must be used as close to the
drive’s output terminals as possible. The shield must be solidly connected to the
PE terminal of the drive.
• Where the shielded motor cable exits the enclosure, an EMC-tested cable
clamp, or metal conduit must be used to solidly connect the cable shield to the
enclosure.
• The shield on the motor side must be solidly connected to the motor housing
with an EMC-tested cable clamp, or conduit, providing good conductivity from
the cable shield to the motor housing.
Motor Connections
Figure C.2
Shielded Enclosure
U/T1
V/T2
W/T3
= EMC Tested Shielded Cable Clamp (or Metal Conduit)
Motor Wiring
TB2
DC+
W/T3
1
3 4 5 6 7 8 9 10 11
2
V/T2
U/T1
DC–
BR+
T/L3
S/L2
R/L1
BR–
FAULT
READY
Ground Terminal – PE
4 Wire Shielded Motor Cable
Ground to Motor Housing
Summary of Contents for Allen-Bradley 160 SSC Series
Page 12: ...1 6 Getting Started End of Chapter ...
Page 58: ...5 20 Parameters and Programming End of Chapter ...
Page 66: ...A 4 Specifications End of Chapter ...
Page 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Page 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Page 82: ...C 6 CE Conformity End of Chapter ...
Page 87: ......