Publication 1734-UM015A-EN-E - November 2009
DeviceLogix Capabilities
81
The following table shows this data for the Logic Supervisor, Timer, and
Counter function blocks.
Note that there is only one Logic Supervisor and its instance is always "1".
If you are using RSLogix 5000, you can send a message by using the MSG
instruction.
Function Block
Class
Code
Instance
Attribute
Data Length
Logic Supervisor
0x30E
1
Logic Enable (0x01)
1 byte
Timer Function
Block
0x30A
Displayed in
editor
Preset Time (0x04)
2 bytes
Elapsed Time (0x07)
2 bytes
Time Base (0x08)
1 byte
0 = 1 ms (default)
1 = 10 ms
Counter Function
Block
0x309
Preset Value (0x05)
2 bytes
Count Value (0x07)
2 bytes
Maximum Input
Frequency (0x08)
2 bytes
Summary of Contents for 1734-8CFGDLX
Page 6: ...Publication 1734 UM015A EN E November 2009 4 Table of Contents Notes ...
Page 10: ...Publication 1734 UM015A EN E November 2009 8 Preface Notes ...
Page 16: ...Publication 1734 UM015A EN E November 2009 14 Introduction Notes ...
Page 109: ...Publication 1734 UM015A EN E November 2009 Peer Data Maps 107 Notes Allen Bradley HMIs ...
Page 110: ...Publication 1734 UM015A EN E November 2009 108 Peer Data Maps Notes ...
Page 111: ...Allen Bradley HMIs ...