Publication 1734-UM015A-EN-E - November 2009
Troubleshooting
87
Network Status
DeviceLogix Status
I/O Status
Indication
Description
Recommended action
Off
Device is not online:
- Device has not completed
dup_MAC-id test.
- Device not powered – check
module status indicator.
Apply power to device, wait for
MAC_id to complete, and correct,
as needed.
Green
Device is online and has one or more
I/O connections in established state.
None.
Flashing
green
Device is online but has no
connections in established state.
None.
Flashing red
One or more I/O connections are in
the timed-out state.
Check for I/O module failure, and
correct, as needed.
Red
Critical link failure – failed
communication device. Device
detected error that prevents it from
communicating on the network.
Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.
Flashing
red/green
Device is in self-test.
None.
Indication
Description
Recommended action
Off
DeviceLogix program is not
controlling outputs.
None.
Green
DeviceLogix program is controlling
outputs.
None.
Flashing
green
At least one input in DeviceLogix
program is forced on/off.
None.
Indication
Description
Recommended action
Off
I/O is inactive.
None.
Yellow
I/O is active and under control.
None.
Summary of Contents for 1734-8CFGDLX
Page 6: ...Publication 1734 UM015A EN E November 2009 4 Table of Contents Notes ...
Page 10: ...Publication 1734 UM015A EN E November 2009 8 Preface Notes ...
Page 16: ...Publication 1734 UM015A EN E November 2009 14 Introduction Notes ...
Page 109: ...Publication 1734 UM015A EN E November 2009 Peer Data Maps 107 Notes Allen Bradley HMIs ...
Page 110: ...Publication 1734 UM015A EN E November 2009 108 Peer Data Maps Notes ...
Page 111: ...Allen Bradley HMIs ...