DeviceLogix Capabilities
79
Enable/Disable Logic
For logic to execute, it must be enabled. While editing online with RSNetWorx
for DeviceNet, you can enable logic.
Logic Enable On
Use the Logic Enable On function to notify the device to start processing the
stored logic diagram. To set Logic Enable On, select Communications > Logic
Enable On.
Logic Enable Off
Use the Logic Enable Off option to notify the device to stop executing the
logic program. When you select this option, the device enters an idle state,
turning off the Logic Enable Bit in the produced data. The Logic Enable bit in
the Produced I/O assembly of the device reflects a 0 or 1 for Logic Enable
Off or Logic Enable On. To set Logic Enable Off, select Communications >
Logic Enable Off.
Dependent Mode
Logic will also be enabled or disabled if the Dependent Mode parameter is
Enabled. In this case, logic will execute following the state of the owning
connection. When the connection is in RUN, the logic is enabled. When the
connection is in Idle, Fault, or non-existent, logic is disabled.
You can also enable or disable logic through explicit messages from the
owning controller. See
.
Summary of Contents for 1734-8CFGDLX
Page 6: ...Publication 1734 UM015A EN E November 2009 4 Table of Contents Notes ...
Page 10: ...Publication 1734 UM015A EN E November 2009 8 Preface Notes ...
Page 16: ...Publication 1734 UM015A EN E November 2009 14 Introduction Notes ...
Page 109: ...Publication 1734 UM015A EN E November 2009 Peer Data Maps 107 Notes Allen Bradley HMIs ...
Page 110: ...Publication 1734 UM015A EN E November 2009 108 Peer Data Maps Notes ...
Page 111: ...Allen Bradley HMIs ...