Publication 1734-UM015A-EN-E - November 2009
40
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
You can select other produced assemblies:
•
Produced assembly instance 4 is the first byte of produced assembly
instance 101 (Data [0]).
•
Produced assembly instance 111 is the first eight bytes of produced
assembly instance 101 (Data [0]…[7]).
You can select other consumed assemblies:
•
Consumed assembly instance 34 is the first byte of consumed assembly
instance 102 (Data [0]).
•
Consumed assembly instance 112 is the first eight bytes of consumed
assembly instance 102 (Data [0]…[7]).
Default Data Map - Consumed Assembly Instance 102
Message Size: 20 Bytes
Bit
7
6
5
4
3
2
1
0
Data [0]
Pt 07
Pt 06
Pt 05
Pt 04
Pt 03
Pt 02
Pt 01
Pt 00
Data [1]
CNB 07 CNB 06 CNB 05 CNB 04 CNB 03 CNB 02 CNB 01 CNB 00
Data [2]
Reserved
Data [3]
Data [4]
Consumed Network Analog Word 0
Data [5]
Data [6]
Consumed Network Analog Word 1
Data [7]
Data [8]
Consumed Network Analog Word 2
Data [9]
Data [10]
Consumed Network Analog Word 3
Data [11]
Data [12]
Consumed Network Analog Word 4
Data [13]
Data [14]
Consumed Network Analog Word 5
Data [15]
Data [16]
Consumed Network Analog Word 6
Data [17]
Data [18]
Consumed Network Analog Word 7
Data [19]
Where: Pt = value to be applied to the output point, CNB = Consumed Network Bit
Summary of Contents for 1734-8CFGDLX
Page 6: ...Publication 1734 UM015A EN E November 2009 4 Table of Contents Notes ...
Page 10: ...Publication 1734 UM015A EN E November 2009 8 Preface Notes ...
Page 16: ...Publication 1734 UM015A EN E November 2009 14 Introduction Notes ...
Page 109: ...Publication 1734 UM015A EN E November 2009 Peer Data Maps 107 Notes Allen Bradley HMIs ...
Page 110: ...Publication 1734 UM015A EN E November 2009 108 Peer Data Maps Notes ...
Page 111: ...Allen Bradley HMIs ...