33
Publication 1734-UM015A-EN-E - November 2009
Chapter
4
DeviceLogix for POINT I/O and ArmorPOINT
I/O on DeviceNet
About This Chapter
This chapter provides information on the following:
•
Offline Configuration using RSNetworx for DeviceNet
•
Online Configuration using RSNetWorx for DeviceNet
•
Offline Configuration using
RSNetworx for DeviceNet
This section is not a substitute for RSNetworx or DeviceNet scanner and
adapter publications. It is suggested that you have those publications available
while performing the procedures in this section See
for a
list of related publications.
This section describes the setup of a DeviceNet network using RSNetworx for
DeviceNet when the module is not connected to the network.
When configuring the module in the Offline mode, you must place all nodes
on the network in the View window manually. Use the Hardware tree to find
each module and place it into the View window. This can be done by
double-clicking the module or dragging it to the View window.
If using a POINT I/O or ArmorPOINT I/O DeviceNet adapter, make sure
you select Adapter for the main DeviceNet network, and Scanner for the
Pointbus backplane.
Summary of Contents for 1734-8CFGDLX
Page 6: ...Publication 1734 UM015A EN E November 2009 4 Table of Contents Notes ...
Page 10: ...Publication 1734 UM015A EN E November 2009 8 Preface Notes ...
Page 16: ...Publication 1734 UM015A EN E November 2009 14 Introduction Notes ...
Page 109: ...Publication 1734 UM015A EN E November 2009 Peer Data Maps 107 Notes Allen Bradley HMIs ...
Page 110: ...Publication 1734 UM015A EN E November 2009 108 Peer Data Maps Notes ...
Page 111: ...Allen Bradley HMIs ...