background image

Preaction Sprinkler DS21-24

für Nassanlagen

Maße in 

mm

;    Gewicht in 

kg/St.

Preaction Sprinkler DS21-24

for wet pipe systems

dimensions  in 

mm;    weight in kg/pc

technical data:

spray characteristics .....................spray sprinkler SP, pendent

response sensitivity .............................fast response RTI < 50

release temperature ...........................................................68 °C

operating pressure .....................................................min. 3 bar

sprinkler body ...........................................brass, chrome-plated

coverage area each Preaction Sprinkler .................max. 9 m²

K factor Preaction Sprinkler ....................................................57

note:

The VdS must agree to the application of Preaction

Sprinklers. (Not required in separated rooms of the fire

hazard class LH and OH with a maximum base area of

30 m²)

Techn. Daten:

Sprühcharakteristik ..................Schirmsprinkler SP, hängend

Ansprechempfindlichkeit ................Fast-Response RTI < 50

Auslösetemperatur ............................................................68 °C

Betriebsdruck ..............................................................min. 3 bar

Sprinklerkörper ...........................................Messing, verchromt

Schutzfläche je Preaction Sprinkler ..........................max. 9 m²

K-Wert Preaction Sprinkler .....................................................57

Hinweis:

Der  Einbau  der  Preaction  Sprinkler  ist  mit  dem  VdS  abzu-

stimmen.  (Nicht  erforderlich  in  abgetrennten  Räumen  der

Brandgefahrenklasse  LH  und  OH  mit  einer  maximalen

Grundfläche von 30 m².)

Bezeichnung

designation

Art.-Nr.

order no.

Gewicht

weight

Preaction Sprinkler DS21 - 68 °C-24

84 4085

2,3

G4870031

*

*

*

U11-1"

U12-1"

oder

or