44
ROBOVENT • SPIRE SERIES OWNER’S MANUAL
SECTION 900
Maintenance
FIGURE 37
FIGURE 39
FIGURE 37
FIGURE 38
15. Remove lock-out and turn power to machine back
on at the disconnect. Start blower, listen for any
abnormal vibration or excess noise.
16. Record differential pressure of filters once the
machine is at full speed.
17. Locate the smoke detector, it will be mounted
behind the access panel on the rear of the unit
below the pulsing system air tank.
a. Inspect the smoke detector and mount for any
obvious signs of damage or dust build up.
b. To test the smoke detector, turn the test indicator
to TEST 1, while the unit is running. (See Figure 36
and 37). After 5-10 seconds the smoke detector
alarm should trigger, red light on the control
cabinet, motor will shut down, intake damper,
if equipped will close, alarm button on HMI will
turn red. After confirming the previous return test
indicator to Normal.
c. The smoke detector should shut the unit down
and go into alarm. If the unit is equipped with
dampers, the dampers will close. Ensure the
dampers close all the way. (see Figure 38).
d. Once you have confirmed the above operations,
return the smoke detector to normal mode.
e. The unit should now be out of alarm state. Turn
the system back on to ensure the unit restarts.
Inspect the damper to ensure it fully opens on
start up. (see Figure 39).
18. Now that all checks have been completed, return
to normal 'ready' condition by turning blower off
(indicated by a steady blue light).
Summary of Contents for Spire MLS-01-5500-10
Page 2: ......
Page 6: ......
Page 7: ...ROBOVENT SPIRE SERIES OWNER S MANUAL 7 SECTION 100 Important Safety Instructions ...
Page 9: ...SECTION 200 Glossary of Terms ...
Page 13: ...SECTION 300 Features of the Spire Series Collector ...
Page 18: ...18 ROBOVENT SPIRE SERIES OWNER S MANUAL ...
Page 19: ...SECTION 400 Receiving Inspection ...
Page 21: ...SECTION 500 Installation ...
Page 26: ...26 ROBOVENT SPIRE SERIES OWNER S MANUAL ...
Page 27: ...SECTION 600 Start up Commissioning ...
Page 31: ...SECTION 700 System Balancing ...
Page 39: ...SECTION 900 Maintenance ...
Page 52: ...52 ROBOVENT SPIRE SERIES OWNER S MANUAL ...
Page 53: ...ROBOVENT SPIRE SERIES OWNER S MANUAL 53 SECTION 1000 Troubleshooting ...
Page 58: ...58 ROBOVENT SPIRE SERIES OWNER S MANUAL ...
Page 59: ...APPENDIX A General Wiring Diagrams ...
Page 65: ...APPENDIX B Parts List ...
Page 66: ...B 2 ROBOVENT SPIRE SERIES OWNER S MANUAL APPENDIX B Parts List C D E F G M L K J I H A B ...