Troubleshooting
(continued)
Cartridge filters load up but no dust in the dust tray. Check the following:
1. Check that the FSS is working properly.
2. Check for oil or moisture on the filter media. If oil or moisture exists in the air supply
it will transfer to the cartridge.
3. In some cases very high oil content is introduced in the welding process causing
the oil to vaporize. This will cause the cartridge filters to load up prematurely. In
this situation the best solution is to remove most of the oil from the parts before
they are welded. Call the RoboVent Service Department at 1-866-ROBOVENT for
more information.
ePad Controller display reads “0” or has a consistently low reading.
1. Check that the clear tubing from the Controller has not come loose from either of the
two NPT fittings.
2. Check for a pinched line in the clear plastic tubing from the Controller.
ePad Controller consistently displays a high reading.
1. Check for a pinched line in the clear plastic tubing from the Controller.
2. Filters are loaded and need changing.
Summary of Contents for FloorSaver Series
Page 2: ......
Page 29: ...ROBOVENT FUSION 4 5 SERIES OWNER S MANUAL 65 SECTION 1000 Motor Greasing Guide ...
Page 38: ...ROBOVENT DFS SERIES OWNER S MANUAL ...
Page 41: ...APPENDIX A ePad Electronic Programmable Controller Instruction Manual ...
Page 51: ...APPENDIX B General Wiring Diagram ...
Page 52: ...B 1 ROBOVENT DFS SERIES OWNER S MANUAL APPENDIX B General Wiring Diagram Single Blower ...
Page 53: ...ROBOVENT DFS SERIES OWNER S MANUAL B 2 APPENDIX B General Wiring Diagram Double Blower ...
Page 54: ......
Page 55: ...APPENDIX C Parts List ...
Page 58: ......
Page 59: ......