Assembly
Operating manual neoTower® Premium L / 03.2017
4.3.5 Connecting the generation unit
(neoTower® 50.0 Standard,
neoTower® 50.0 High temperature)
When connecting the system to the heating system it is
necessary to follow the appropriate hydraulic diagram.
D
“12.1 Hydraulic diagrams” (page 36).
Always match the connections to the identifiers on the
generation unit.
Pay attention the to connection sizes and type when
connecting the lines.
Generation unit connection sizes
Connection
Connection size and type
Buffer water return line
2” MALE THREAD
Buffer water supply line
2” MALE THREAD
Condensate
3/4” male thread
Flue gas
DN 80/100
Exhaust air
DN 200
Gas
1” male thread
D
ATTENTION!
Risk of damage caused by improper connection of lines.
Fixed supply lines will transfer vibrations to the building.
The permissible sound insulation values will be exceeded.
Vibrations may damage the supply lines.
A
Only use flexible lines for all the lines connected to the
generation unit.
A
Pay close attention when matching the lines and
connections.
Buffer water return line
A
Connect the line to the return line of the buffer tank.
A
Connect the line to the “Buffer water return line”
connection on the generation unit.
Buffer water supply line
A
Connect the line to the supply line of the buffer tank.
A
Connect the line to the “Buffer water supply line”
connection on the generation unit.