Assembly
Operating manual neoTower® Premium L / 03.2017
4.2.2 Premises
The premises must meet the following requirements:
B
The installation location must comply with the effective
applicable laws and regulations for boiler rooms
(e.g. in Germany, the ordinance for heat-producing
appliances (Feuerstättenverordnung)).
B
The substrate on which the generation unit is to be
installed must be flat, even, solid, dry and load-bearing.
B
The ambient temperature must be between
+10 °C and +30 °C.
B
The system must be protected against frost and the
elements.
The following are not permitted:
B
Installation on floating screed.
B
Operation of washing machines or tumble dryers in the
same room.
B
Storage of explosive or highly flammable materials
(e.g. paper, paints, petrol) within the installation
location.
B
Use of aggressive substances (e.g. sprays, solvents,
chlorinated cleaning agents, paints, adhesives) in the
vicinity of the system.
If the system is installed in vaulted cellars or relatively
empty spaces with smooth walls, there is a risk of noise and
sound resonance.
The system must be positioned so that the following
requirements are fulfilled:
B
None of the system’s ventilation or extraction devices
may be blocked or closed.
B
The emergency stop switch must always be accessible.
B
The minimum clearance to the generation unit
(> 700 mm on all sides) must be maintained.
B
The minimum clearance to the calorific value heat
exchanger
1
(> 700 mm on all sides) must be maintained.
1
only with variant "neoTower® 50.0 Calorific value"
Space requirement for neoTower® Premium L
2180
798
> 700
> 700
> 700
> 700
1670
Space requirement for calorific value heat exchanger
1
?
> 700
> 700
> 700
> 700
425
?
1
only with variant "neoTower® 50.0 Calorific value"