WiNG-MGR v2 User Guide
49
3
Web Interface
3.7.3 BACnet
If the WiNG-MGR will communicate via the BACnet, configure the necessary options here.
Figure 3.24
BACnet Configuration
Option
Description
Pics
Click this link to view the Bacnet identifiers and objects supported by
the WiNG-MGR.
Device ID
To enable BACnet, assign a unique number between 1 and 4194302
to identify this BACnet device on the network.
If you enter a 0 in this field BACnet will be disabled.
Default: 0 (Disabled)
Device Name
Assign a name - up to 38 characters - to the unit for BACnet
discovery and integration.
Description
Add any additional details about the device, up to 38 characters.
Location
Designate the physical location of the unit.
UDP Port
Enter a 0 to specify port 47808 (0xBAC0) as the UDP port. If another
port is specified by your application, enter that value here.
Default: 0 (47808)
Register as Foreign
Device at IPv4
IP address of the master device with which you’re trying to
communicate. Requires a BBMD for foreign device discovery.
Registration TTL
Time, in seconds, for foreign device discovery.
MS/TP Max Master
Only for EIA-485 Bacnet MS/TP mode; the Max Master is the highest
BACnet station ID the WiNG manager will attempt to discover. This
should match the highest station ID in the MS/TP ring. All devices in
the ring should have the same Max Master value configured.
Table 3.13
BACnet Configuration Options
Summary of Contents for WiNG-MGR v2
Page 4: ...4 WiNG MGR v2 User Guide 800 518 1519 ...
Page 14: ...14 WiNG MGR v2 User Guide 800 518 1519 1 System Overview ...
Page 74: ...74 WiNG MGR v2 User Guide 800 518 1519 5 WiNG RXT ...
Page 78: ...78 WiNG MGR v2 User Guide 800 518 1519 ...
Page 82: ...82 WiNG MGR v2 User Guide 800 518 1519 ...
Page 86: ...86 WiNG MGR v2 User Guide 800 518 1519 C Alternate Channel Pair Communications ...
Page 90: ...90 WiNG MGR v2 User Guide 800 518 1519 D Troubleshooting ...
Page 94: ...94 WiNG MGR v2 User Guide 800 518 1519 E Technical Specifications ...