rletech.com
WiNG-MGR v2 User Guide
33
3
Web Interface
Gain
WiNG-ANLG Sensors
- Using the formulas below, adjust the gain
value appropriately to fine tune your WiNG-ANLG sensor’s
accuracy.
For 4-20mA sensors:
Gain = (Sensor high range value – sensor low range value) ÷ 3085
Example
: Temperature sensor with a sensing range of 5-120°F
Gain = (120 - 5) ÷ 3085 = 0.0373
For 0-5V and 0-10V sensors:
Gain = (Sensor high range value – sensor low range value) ÷ 3856
Example
: Temperature sensor with a sensing range of 5-120°F
Gain = (120 - 5) ÷ 3856 = 0.0298
Offset
WiNG-ANLG Sensors
- Using the formulas below, adjust the offset
values appropriately to fine tune your WiNG-ANLG sensor’s
accuracy.
For 4-20mA sensors:
Offset = Sensor low range – ((Sensor high range value – sensor
low range value) ÷ 4)
Example:
Temperature sensor with a sensing range of 5-120°F
Offset = 5 - ((120-5) ÷ 4) = -23.75
For 0-5V and 0-10V sensors:
Offset = Sensor low range
Example:
Temperature sensor with a sensing range of 5-120°F
Offset = 5
Footer Buttons -
Remember to click the
Submit Changes
button for the sensor you’re
currently configuring before you move to another sensor’s configuration page.
<Previous Sensor
Configure the previous sensor in the list.
Next Sensor>
Configure the next sensor in the list.
Option
Description
Table 3.4
Individual Sensor Page - Sensor Configuration Tab Options
Summary of Contents for WiNG-MGR v2
Page 4: ...4 WiNG MGR v2 User Guide 800 518 1519 ...
Page 14: ...14 WiNG MGR v2 User Guide 800 518 1519 1 System Overview ...
Page 74: ...74 WiNG MGR v2 User Guide 800 518 1519 5 WiNG RXT ...
Page 78: ...78 WiNG MGR v2 User Guide 800 518 1519 ...
Page 82: ...82 WiNG MGR v2 User Guide 800 518 1519 ...
Page 86: ...86 WiNG MGR v2 User Guide 800 518 1519 C Alternate Channel Pair Communications ...
Page 90: ...90 WiNG MGR v2 User Guide 800 518 1519 D Troubleshooting ...