Leak Threshold
This number represents the uA of current that must be present on
the leak detection sensing cable in order to trigger an alarm.
If you are seeing a large number of false alarms, even after
cleaning the cable, our tech support staff may work with you to
adjust this threshold.
Default = 4
Alarm Delay
The number of seconds that pass between the time the system
goes into alarm and the time that alarm is annunciated.
Relay Upon Alarm
If the sensor goes into alarm, will it activate a relay? If so, designate
which relay or relays it will activate, and check the appropriate
boxes for which conditions the relay should be activated.
Default = None
Settings
Offline Alarm Delay
If the sensor goes offline, how much time should pass before an
alert is generated?
0 = Offline alarms are disabled.
Dewpoint Display
If you have a temperature/humidity sensor, a calculated dew point
can be displayed. Select Yes to activate this option.
Thermistor Type
Use a 10k-2 thermistor with our WiNG-THRM sensor.
Warning Notifications
Temp Over
Enter a high temperature warning threshold - if the temperature
rises above this value, a high temperature warning is generated.
Temp Under
Enter a low temperature warning threshold - if the temperature
drops below this value, a low temperature warning is generated.
Humidity Over
Enter a high humidity warning threshold - if the humidity rises above
this value, a high humidity warning is generated.
Humidity Under
Enter a low humidity warning threshold - if the humidity drops below
this value, a low humidity warning is generated.
Warning Delay
The number of seconds that pass between the time the system
goes into a warning state and the time that warning is annunciated.
Adjustment Settings -
Using the formulas below, adjust the gain and offset values
appropriately to fine tune your sensor’s accuracy.
Temperature Offset
To fine tune the accuracy of the temperature reading, enter an
offset value here. The offset value is a degree amount in 0.1°
increments. Use - for negative offsets.
Humidity Offset
To fine tune the accuracy of the humidity reading, enter an offset
value here. The offset value is a percent humidity amount in 1%
increments. Use - for negative offsets.
Option
Description
Table 3.4
Individual Sensor Page - Sensor Configuration Tab Options
Summary of Contents for WiNG-MGR v2
Page 4: ...4 WiNG MGR v2 User Guide 800 518 1519 ...
Page 14: ...14 WiNG MGR v2 User Guide 800 518 1519 1 System Overview ...
Page 74: ...74 WiNG MGR v2 User Guide 800 518 1519 5 WiNG RXT ...
Page 78: ...78 WiNG MGR v2 User Guide 800 518 1519 ...
Page 82: ...82 WiNG MGR v2 User Guide 800 518 1519 ...
Page 86: ...86 WiNG MGR v2 User Guide 800 518 1519 C Alternate Channel Pair Communications ...
Page 90: ...90 WiNG MGR v2 User Guide 800 518 1519 D Troubleshooting ...
Page 94: ...94 WiNG MGR v2 User Guide 800 518 1519 E Technical Specifications ...