314
Dir = u (timing diagram numbers 1 and 3)
If the updated value PV > SP, then the special function reduces the value of AQ.
If the updated value PV < SP, then the special function increases the value of AQ.
Dir = downwards/- (timing diagram number 2)
If the updated value PV > SP, then the special function increases the value of AQ.
If the updated value PV < SP, then the special function reduces the value of AQ.
With a disturbance, AQ continues to increase / decrease until the updated value PV again
corresponds to SP. The speed with which AQ changes depends on the parameters KC and
TI. If the input PV exceeds the parameter Max., then the updated value PV is set to the
value of Max.. If the PV falls short of the parameter Min., then the updated value PV is set
to the value of Min.
If the input R is set to 1, then the AQ output is reset. As long as R is set, the input A/M
is disabled.
Sampling Time
The sampling time is fixed at 500 ms.
Parameter sets
In order to simplify the use of the PI controller, the parameters for KC, TI and Dir are
already given as sets for the following applications:
Parameter set
Application example
Parameter KC Parameter TI
(s)
Parameter
Dir
Temperature fast
Temperature, cooling control of
small spaces; small volumes
0,5
30
+
Temperature slow
Heating, ventilation, temperature,
cooling control of large spaces;
large volumes
1,0
120
+
Pressure 1
Quick
pressure
change,
compressor control
3,0
5
+
Pressure 2
Slow pressure change, differential
pressure control (flow controller)
1,2
12
+
Full level 1
Vat and/or reservoir filling without
drain
1,0
1
+
Summary of Contents for EXM-12DC-DA-R-HMI
Page 15: ...15 Application 2 Home Security Application 3 Remote monitoring of product level in a tank...
Page 35: ...35 How to change the phone book include phone number and Email address Only for 4G version...
Page 38: ...38...
Page 49: ...49 Step C Download voice section Click menu Tool Record Click Hardware Detect button...
Page 66: ...66 You can read the parameters from the PLC...
Page 68: ...68...
Page 75: ...75 Modbus Poll works as TCP client...
Page 78: ...78 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 79: ...79 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 80: ...80 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 84: ...84 3 Click Read button to read web server configure The default configuration is as follows...
Page 102: ...102 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 103: ...103 Slave3 IP 192 168 0 103 TCP server port 8003 Step 2 Program in master and slave...
Page 115: ...115 Slave1 IP 192 168 0 101 UDP Server port 8001 Slave2 IP 192 168 0 102 UDP Server port 8002...
Page 128: ...128 Network settings You can view the network parameters in such table...
Page 135: ...135 3 Select Ethernet option 4 To search PLC s IP by clicking Search button...
Page 145: ...145 B005 Read the I1 I4 status from the slave1 to the F11 F14 of the master Setting as follows...
Page 146: ...146 B006 Read the I1 IA status from the slave2 to the F21 F24 of the master Setting as follows...
Page 147: ...147 B009 Read the AF1 value from the slave1 to the AF1 of the master Setting as follows...
Page 148: ...148 B010 Read the AF1 value from the slave2 to the AF2 of the master Setting as follows...
Page 260: ...260 E F digital flag status F AF analog flag value...
Page 261: ...261 G M status H AM value...
Page 332: ...332 For example If the Memory Read block had been triggered the Q1 of ELC 12 CPU will be set 1...
Page 411: ...411 Establish the communication between eSmsConfig and EXM WIFI Unit...
Page 426: ...426 7 6 How to configure WIFI connection TCP protocol among EXM WIFI CPUs...
Page 432: ...432 B005 Read the I1 I4 status from the slave1 to the F11 F13 of the master Setting as follows...
Page 433: ...433 B006 Read the I1 I4 status from the slave2 to the F21 F23 of the master Setting as follows...
Page 434: ...434 B009 Read the AF1 value from the slave1 to the AF1 of the master Setting as follows...
Page 435: ...435 B010 Read the AF1 value from the slave2 to the AF2 of the master Setting as follows...
Page 436: ...436...