3095
6
GB
3.3
GAS TRAIN,
(as EN 676)
The gas train is supplied separately, for its adjustment see the enclosed instructions.
3.4
GAS TRAIN ELECTRICITY SUPPLY
The gas train’s power cables can be fed to the right or left
of the burner, as illustrated in figure 5.
Depending on the entry point, the cable clamp with pres-
sure test point (1) and simple cable clamp (2) may need
swapping over.
Consequently, you must make sure:
³
cable clamp (1) is positioned correctly;
³
the tube is positioned correctly so that there are no re-
strictions likely to impede air flowing to the pressure
switch.
WARNING
If necessary, cut the tube to the right size.
3.5
GAS FEEDING LINE
GAS TRAIN
CONNECTIONS
USE
TYPE
CODE
INLET
OUTLET
MBDLE 410 B01
3970549
Rp 1 1 / 4
Flange 3
Natural gas
≤
200kW and LPG 160
–
330 kW
MBDLE 412 B01
3970550
Rp 1 1 / 4
Flange 3
Natural gas
≤
300 kW
MBDLE 415 B01
3970558
Rp 1 1 / 2
Flange 3
Natural gas
≥
300 kW
2
1
2
1
D7113
Fig. 5
M2
Fig. 6
D5209
1
2
3
M1
5
6
7
4
8
1
– Gas supply pipe
2
– Manual
cock
(charged to the installer)
3
– Gas pressure gauge
(charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety
valve
7
– Pressure
governor
8
– Adjusting
valve
M1
– Gas-supply pressure test point
M2
– Pressure coupling test point