3095
2
GB
1.
BURNER DESCRIPTION
One stage gas burner.
1.1
BURNER EQUIPMENT
Flange with insulating gasket . . . . . No. 1
Screws and nuts for flange to be fixed to boiler . . . No. 4
Screw and nut for flange . . . . . . . . . No. 1
7 pin plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Remote reset connection . . . . . . . . No. 1
1.2
ACCESSORIES
SOFTWARE DIAGNOSTIC KIT
A special kit is available that, by an optical link to a PC, shows the burner life together with operating hours, type
and number of failures, serial number, etc.
To visualise the diagnostics proceed as follows:
³
Connect the kit supplied separately to the control box socket.
Reading of the information begins when the software programme included in the kit starts.
REMOTE RESET KIT
The burner has a remote reset kit (
RS
) consisting of a connection and a push-button operating at a
distance of 20 metres max.
In order to install it remove the protective lock-out installed at the factory and insert the lock-out supplied
with the burner (see electrical diagram on page 7).
MULTIBLOC ROTATION KIT
There is a special kit available that can be used to install the burner turned 180°, as illustrated on page 5 in
position 5 in the section entitled "
3.1 WORKING POSITION
". This kit is designed to ensure the gas train
valve works properly. The kit must be installed in conformity with laws and local regulations.
1
– Air pressure switch
2
– 6 pole socket for gas train
3
– Control box with 7 pole socket
4
– Reset button with lock-out lamp
5
– Head holder assembly
6
– Pressure test point
7
– Flange with insulating gasket
8
– Air damper adjustment assembly
9
– Servomotor
10
– Motor
³
The burner meets protection level of IP X0D (IP 40), EN 60529.
³
CE marking according to Gas Appliance directive 90/396/EEC; PIN
0085BM0114
.
According to directives: EMC 89/336/EEC, Low Voltage 73/23/EEC and Machines 98/37/EEC.
³
Gas train according to EN 676.
³
The burner is approved for intermittent operation as per Directive EN 676.
Fig. 1
D7110
8
6
1
4
2
5
10
3
7
9