62
MENU
DEFAULT VALUE
FACTORY SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCES
LEVEL NOTES
SET
VALUE
NIGHT COMP
FUNCTION NOT
ACTIVE
FUNCTION NOT
ACTIVE
FUNCTION ACTIVE
INSTALLER
If EXT PROBE
connected
Only with ON/
OFF thermostat,
not for REC10 or
Ricloud.
Described on
page 48
CURVE SLOPE
2.0
1.0
3.0
INSTALLER
If EXTERNAL
PROBE
connected,
request
type TA and
zone high
temperature
type
Only for ON/OFF
thermostat and
HIGH temperature
system
0.4
0.2
0.8
INSTALLER
If EXTERNAL
PROBE
connected,
request
type TA and
zone low
temperature
type
Only for ON/OFF
thermostat and
LOW temperature
system
BUILDING TYPE
5min
5min
20min
INSTALLER
Only if
EXT PROBE
connected
Described on
page 48
OUTDOOR REACTIVITY
20
0
256
INSTALLER
Only if
EXT PROBE
connected
Described on
page 48
RANGE RATED
MAX CH
MIN
MAX CH
INSTALLER
Not used
CALIBRATION
INSTALLER
The calibration
parameter allows
the output of
the boiler to be
adjusted by fan
speed
MIN
See boiler instruction
INSTALLER
Min adjusts the
minumum output
of
the boiler by fan
speed
MAX
See boiler instruction
INSTALLER
Max adjusts the
DHW
maximum output
of the
boiler by fan
speed
MAX CH
See boiler instruction
INSTALLER
Max CH adjusts
the CH maximum
output of the
boiler by fan
speed
COMBUSTION ANALYSIS
INSTALLER
ACTIVATE FUNCTION
INSTALLER
Described on
page 52
DEACTIVATE FUNCTION
INSTALLER
Described on
page 52
MAX SPEED
MAX
INSTALLER
RANGE RATED SPEED
RANGE RATED
INSTALLER
MIN SPEED
MIN
INSTALLER