37
Fig. 17 Twin flue system 3” (Ø 76,2 mm) with vertical terminal
3” (Ø 76,2 mm) CPVC (L)
Max length
82+82 ft (24.99+24.99 m)
Terminal length (L1)
part no 197009
1.67 ft (0.5 m)
part no 197107
2.67 ft (0.8 m)
part no 197117
3.67 ft (1.1 m)
fig. 17
increaser 2”-3”
Fig. 18 Vertical twin flue system 3” (Ø 76,2 mm) with terminal
bend CPVC for pitched roof (L)
Max length
82+82 ft (24.99+24.99 m)
90° bend
6 ft (1.83m)
the expressed lengths are without the terminations
Vertical twin flue system 3” (Ø 76,2 mm) with terminal bend PP
for pitched roof (L)
Max length
82+82 ft (24.99+24.99 m)
90° bend
6 ft (1.83m)
the expressed lengths are without the terminations
fig. 18
increaser 2”-3”
Fig. 19 Vertical twin flue system 3” (Ø 76,2 mm) with terminal
bend CPVC for flat roof (L)
Max length
82+82 ft (24.99+24.99 m)
90° bend
6 ft (1.83m)
the expressed lengths are without the terminations
fig. 19
increaser 2”-3”
Fig. 20 Twin flue system 3” PP (Ø 76,2 mm)
Max length (L)
82+82 ft (24.99+24.99 m)
Max length (L1)
76+76 ft (23.16+23.16 m)
90° bend
6 ft (1.83m)
the expressed lengths are without the terminations
8.10
increaser
2”-3”
Min 24"
OUT
IN
18"
4"
L1
fig. 20
Multi Family boiler installation
In Multi-Family installations where venting assemblies pass
through fire rated floors or partitions, submit requests directly
to Duravent ([email protected]) or Security Chimneys
([email protected]) for an approved engineered
design by the venting manufacturer. The application must also
be in compliance with local codes and the local authority having
jurisdiction.