53
- access the technical parameters as explained in the
section “11.6 Access to the technical parameters”
- select COMBUSTION ANALYSIS with the “up” and “down”
buttons, confirming the selection
WEATHER COMPENSATION
PARAMETERS
RANGE RATED
CALIBRATION
COMBUSTION ANALYSIS
INSTALLER
TECHNICAL
CALIBRATION
RANGE RATED
WEATHER COMPENSATION
PARAMETERS
COMBUSTION ANALYSIS
TECHNICAL
INSTALLER
- select ACTIVATE/DEACTIVATE FUNCTION with the “up” and
“down” buttons, confirming the selection.
COMBUSTION ANALYSIS
INSTALLER
ACTIVATE FUNCTION
ACTIVATE FUNCTION
COMBUSTION ANALYSIS
INSTALLER
- Note: the combustion analysis function can also be acti-
vated by pressing the SW1 button on the electronic board
MAIN PCB (this requires removing the tap (C) from the cover
of the instrument panel to access the electrical compo-
nents).
C
Wait for the burner to ignite.
The boiler will operate at maximum heating output and it will
be possible to regulate the combustion.
- Insert the analyzer probe in the specific positions on the
air distribution box, after removing the two taps (A).
-
A
Perform the combustion check verifying that the CO
2
values correspond to those indicated in the ”5.3
- Once checks are completed, remove the analyzer
probe and close the combustion analysis sockets with
appropriate caps and screw.
9
WARNING
: If the value displayed is different from the one
shown in the section “5.3 Technical data” DO NOT MAKE ANY
ADJUSTMENT ON THE GAS VALVE, please contact the Technical
Assistance Centre.
9
WARNING
: The gas valve DOES NOT REQUIRE ADJUSTMENTS and
the possible tampering can cause a malfunction or failure of
the boiler which may result in substantial property damage,
severe personal injury or death.
NOTICE
: When the combustion analysis function is in progress
all the heat requests are inhibited and a scrolling message
appears at the foot of the main page of the front control.
When the checks are completed:
- set the boiler to “DHW” or “CH&DHW” mode
- regulate the heat request temperature values according
to the customer’s needs.
IMPORTANT
The combustion analysis function is active for a time
limit of 15 minutes; the burner shuts down if an outlet
temperature of 203°F (95° C) is reached. It will ignite again
when the temperature falls below 167°F (75° C).
9
In case of a low temperature system we recommend carrying
out the efficiency test, setting the boiler STATE to DHW mode,
opening the hot water tap to full capacity and setting the
temperature of the domestic hot water to the maximum.
11.22 Lights and faults
In the unlikely event of boiler fault, the appliance will enter a
final or temporary fault condition, whereby it will shut down
and a
WARNING
triangle
will appear on the left side of the UI
screen. Use the arrow buttons on the user inferface to navigate
to the
WARNING
triangle, and press “ENTER”. Then follow the
instructions/advice as shown on the user interface screen.
18/05/2013
12:17
MENU
INFO
SET
107
°F
FRI
PLANT
HOT WATER TEMPERATURE
STATE
18.85 psi
MENU
STATE
SET
INFO
PLANT
HOT WATER TEMPERATURE
FRI
The faults description screen is automatically displayed once the
display illumination time has elapsed without any button being
pressed.
Press the “up” and “down” buttons to display the descriptions
of any other faults that may be present.
Reset function
In order to reset the boiler’s operation in the event of a fault, it
is necessary to access the fault description screen. If the lockout
is of a non-volatile type that requires a reset procedure, this will
be indicated on the screen, and can be performed
by pressing
the “ENTER
” button on the front control.
At this point, if the correct operating conditions have been
restored, the boiler will restart automatically.
There are a maximum of 3 consecutive attempts at a release
by the front control, should it go through all 3 attempts to reset
the fault, the appliance will need to be disconnected briefly
from the electrical supply in order to carry out any further reset
attempts. Once the electrical supply has been restored, further
attempts at reset can be carried out.
E020
LIMIT THERMOSTAT
RESET ATTEMPTS EXHAUSTED
LIMIT THERMOSTAT
RESET ATTEMPTS EXHAUSTED