List of combustion faults
ERROR
CODE
DISPLAYED
COLOUR
ERROR MESSAGE
ERROR TYPE
DESCRIPTION OF ERROR TYPE
E021
red
iono error
temporary
These are temporary errors that if they occur
several times in an hour they become a hard
lockout; the error E097 is displayed and is
followed by post-purging for 45 seconds at the
fan’s maximum speed.
It is not possible to release the error before the
end of the post-purging unless the boiler’s
power supply is switched off.
E022
red
iono error
temporary
E023
red
iono error
temporary
E024
red
iono error
temporary
E067
red
iono error
temporary
E088
red
iono error
temporary
E097
red
iono error
final
E085
red
ACC monitor error
temporary
➞
final (see condition in
the beside column)
These are temporary errors that if they
occur several times in an hour they become
definitive; the last error to occur is displayed
and is followed by a post-purging of 5 minutes
at the fan’s maximum speed.
It is not possible to reset the error before the
end of the post-purging unless the boiler’s
power supply is switched off.
E094
red
ACC monitor error
temporary
➞
final (see condition in
the beside column)
E095
red
ACC monitor error
temporary
➞
final (see condition in
the beside column)
E058
red
supply voltage fault
temporary
These are temporary faults that restrict the ig-
nition cycle.
E065
red
error modulation current
temporary
E086
red
error flue obstruction
temporary
Temporary fault reported during the post ven-
tilation. It is maintained a post ventilation of 5
min at maximum fan speed.
Boiler faults list
ERROR
CODE
DISPLAYED
COLOUR
ERROR TYPE
DESCRIPTION OF ERROR TYPE
E010
yellow
final
flame lockout/ACF electronic fault
E011
yellow
temporary
parasitic flame
E020
red
final
water high limit/heat exchanger thermostat
E030
red
final
fan fault
E040
yellow
final
low water cutoff - check system water pressure
E041
yellow
temporary
low water cutoff - check system water pressure
E042
yellow
final
low water cutoff fault
E060
yellow
temporary
domestic hot water sensor fault (combi model)/indirect tank sensor fault
(heating only model)
E070
yellow
temporary/
final
final
fault supply sensor/
high limit supply sensor
supply/return sensor differential error
E077
red
temporary
external error contact
E080
yellow
temporary/
final/
final
fault return line sensor/
return line sensor high limit/
outlet/return line sensor differential error
E090
red
temporary
final
fault flue gas sensor/air pressure switch
flue high limit sensor
E091
yellow
temporary
need for periodic maintenance
E099
red
final, not resettable
reset attempts exhausted, boiler blocked
red
temporary
water pressure high check system
red
temporary
boiler board communication lost
red
temporary
BUS 485 communication lost
Final= boiler BLOCK, manual reset needed
Transitional= the boiler automatically restores the alarm without any external intervention.