69
SYSTEM MANAGEMENT
4.3.1
Zone control with Depending module
If used on a cascade system, with heating zone control using
DEPENDING thermal module, after carrying out the connections
as described in the Cascade Manual, the following modifications
need to be made.
On the display of the Depending thermal module to which the
zone is connected:
Par. 97
− if configured with value = 1 (use with circulator) it must
be changed to value = 9
− if configured with value = 2 (use with 2-way valve) it must
be changed to value = 8
9
The 97=8 configuration CANNOT be applied to models with a
boiler circulator installed as standard.
Par. 205
By default the parameter is disabled. To enable the recognition
of the zone the value must be changed from "DIS" to "ENA" and
confirmed.
When the modifications are complete the following new func-
tions will be available on the display of the device:
− in the "Information" menu the number of the connected
zone appears (zone of the dependent), from where it is
possible to display information about it;
− in the "Settings menu" two new lines will be displayed:
− "Config. Zone Dep."
− "Clim. Curve Zone Dep."
− The following new row will apper in the "Time program"
menu:
− "Program CH Zone Dep."
Cascade connection
SAFETY
THERMOSTAT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
ROOM
THERMOSTAT
FLOW
SENSOR
BUS
MIX VALVE
PUMP
L
L L
N
N L
N
BUS 1
MO1
MANAGING
1
2
3
4
9 10 11 12 13 14 15 16 17 18
5 6 7 8
1
2
3
4
9 10 11 12 13 14 15 16 17 18
5 6 7 8
DEPENDING
MO1
DEPENDING
DEPENDING
MO1
MO1
M03
1
2
3
4
9 10 11 12 13 14 15 16 17 18
5 6 7 8
1
2
3
4
9 10 11 12 13 14 15 16 17 18
5 6 7 8
ACCESSORY MIXED ZONE
BUS 2
BUS 2
BUS 2
SAFETY
THERMOSTAT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
ROOM
THERMOSTAT
FLOW
SENSOR
BUS
MIX VALVE
PUMP
L
L L
N
N L
N
M03
ACCESSORY MIXED ZONE
4.3.2
Deleting dependent zone
To remove a Dependent zone operate in the reverse way to its
installation:
− enter the parameters menu and select the par. 205.
Change its value from "ENA" to "DIS";
− change the par. 97. If par. 97 = 9 change to = 1; if par. 97
= 8 change to = 2.
On the "Information" menu:
− enter "Status zone dep.";
− select the number of the depending zone;
− The "Detection" field will indicate "NO";
− select "Remove zone" changing to "SI" and confirm.
Now in the "Settings" and "Information" menus the depending
zone will no longer be displayed.
The electronic control of the thermal module will automatically
check which zones are connected to the bus.
The menu items of the zone in the electronic control of the ther-
mal module will be available when one or more zone manage-
ment devices are detected.
The electronic control of the thermal module remembers the
zone number detected when a device is connected.
The zone number detected is not automatically removed when
the corresponding accessory is no longer connected.
The zone number needs to be removed manually.
Removing the zone number
− remove the bus connection of the zone to be deleted;
− access the Settings/Zone Config./Zone;
− select the disconnected zone;
− go to Remove Zone;
− press the
►
key to highlight the values, change them to
“Yes“ with the
▲
/
▼
keys, press the
●
key to confirm and
remove the zone from the display menus.
Example:
“
External Zone
”
3
“
Detection
”
“
No
”
“
Remove Zone
”
“
No
”
“
External Zone
”
3
“
Detection
”
“
No
”
“
Remove Zone
”
“
Yes
”
Summary of Contents for Condexa PRO 100
Page 32: ...32 INSTALLATION 7 Position the GAS manifold 8 Secure the GAS manifold to the frame 7 7 8...
Page 33: ...33 INSTALLATION 9 Position the manifold closing plugs from the required side 9 22mm 51mm...
Page 36: ...36 INSTALLATION 7 Position the GAS manifold 8 Secure the GAS manifold to the frame 8 8 7...
Page 37: ...37 INSTALLATION 9 Position the manifold closing plugs from the required side 9 22mm 51mm...