176
OVERVIEW OF THE PARAMETERS
INSTALLATION
MODE MENU – MODES
Point name
Status
Units
Text displayed*
Description
1
m_delay
no/yes
-
Active Delay
Active delay (during mode switch-
ing)
2
m_2ndspt
no/yes
-
Second Setpoint Active
Second Setpoint Active (in unoccu-
pied periods)
3
m_reset
no/yes
-
Active Reset
The reset is active
4
m_limit
no/yes
-
Active Demand Limit
Active demand limit
5
m_ramp
no/yes
-
Active Ramp Charging
Active ramp charging
6
m_cooler
no/yes
-
Active Heater Cooler
Active water exchanger heater
7
m_pmprot
no/yes
-
Active Pump Rotation
Active pump rotation
8
m_pmpper
no/yes
-
Per Pump Active
Periodical pump start-up active
9
m_night
no/yes
-
Low Night Noise Active
Low night noise mode active
10
m_SM
no/yes
-
Active System Manager
Active System Manager
11
m_leadla
no/yes
-
Active Master/Slave
Master/Slave enabled
12
m_auto
no/yes
-
Active Auto-switching
Active auto-switching
13
m_heater
no/yes
-
Active Electric Heater
Active electric heating
14
m_lo_ewt
no/yes
-
Low Heating EWT Lockout
Low heating EWT lockout
15
m_boiler
no/yes
-
Boiler Active
Boiler active
16
m_ice
no/yes
-
Active Ice Mode
Active ice mode
17
m_defr_a
no/yes
-
Active Defrost on Cir A
Active defrost on circuit A
18
m_defr_b
no/yes
-
Active Defrost on Cir B
Active defrost on circuit B
19
m_sst_a
no/yes
-
Circuit A Low Suction
Circuit A low suction temperature
20
m_sst_b
no/yes
-
Circuit B Low Suction
Circuit B low suction temperature
21
m_dgt_a
no/yes
-
Circuit A High DGT
Circuit A high discharge gas tem-
perature
22
m_dgt_b
no/yes
-
Circuit B High DGT
Circuit B high discharge gas tem-
perature
23
m_hp_a
no/yes
-
Cir A High Pressure Bypass
High pressure bypass on circuit A
24
m_hp_b
no/yes
-
Cir B High Pressure Bypass
High pressure bypass on circuit B
25
m_sh_a
no/yes
-
Circuit A low overheating
Circuit A low overheating
26
m_sh_b
no/yes
-
Circuit B low overheating
Circuit B low overheating
* It depends on the selected language (English by default).