145
CONTROL PANEL
INSTALLATION
3.7
Operations and standard control options
3.7.1
Unit start/stop control
Unit status is determined according to a series of factors in-
cluding operation type, active bypasses, open contacts, mas-
ter/slave configuration or alarms triggered by the operating
conditions.
The table below shows the unit control types [ctrl_typ] and
their operating status compared to the following parameters:
Operation type:
This type of operation is selected using the
Start/Stop push-buttons on the user interface.
LOFF
: Local off
L-C
:
Local on
L-SC
: Local scheduling
Rem
: Remote
Net
: Network
Mast
: Master unit
Start/stop control bypass [CHIL_S_S]:
Start/stop control bypass
can be used to control chiller status in Network mode.
−
Control set to stop:
The unit will be stopped.
−
Control set to start
: The unit is started as indicated by
scheduling 1.
Remote start/stop contact status [Onoff_sw]
: Start/stop con-
tact status can be used to control chiller status in Remote op-
eration mode.
Master control [ms_ctrl] type
: When the unit is the master unit.
In a master/slave layout with two chillers, the master unit can
be set to be locally controlled from remote or through network.
Start/stop scheduling [chil_occ]
: Unit occupied or unoccupied
status.
Emergency stop of the network [EMSTOP]
: If activated, the unit
will stop immediately regardless of the active operation type.
General alarm
: The unit will turn off due to a fault.
Active operation type
Parameter status
Result
LOFF
L-C
L-SC
Rem
Net
Mast
Start/Stop
bypass
Remote
start /stop
contact
Master
control
type
Start/Stop
timer
Network
emergency
stop
General
alarm
Control
type
Unit
status
-
-
-
-
enabled
-
-
off
-
-
-
-
-
yes
-
off
active
-
-
-
-
-
-
local
off
active
-
-
-
unoccupied
-
-
local
off
active
-
off
-
-
-
-
remote
off
active
-
-
-
unoccupied
-
-
remote
off
active
deactivated
-
-
-
-
-
network
off
active
-
-
-
unoccupied
-
-
network
off
active
-
-
local
unoccupied
-
-
local
off
active
-
off
remote
-
-
-
remote
off
active
-
-
remote
unoccupied
-
-
remote
off
active deactivated
-
network
-
-
-
network
off
active
-
-
network unoccupied
-
-
network
off
active
-
-
-
-
deactivated
no
local
on
active
-
-
-
occupied
deactivated
no
local
on
active
-
on_cool
-
occupied
deactivated
no
remote
on
active
-
on_heat
-
occupied
deactivated
no
remote
on
active
-
on_auto
-
occupied
deactivated
no
remote
on
active
enabled
-
-
occupied
deactivated
no
network
on
active
-
-
local
occupied
deactivated
no
local
on
active
-
on_cool
remote
occupied
deactivated
no
remote
on
active
-
on_heat
remote
occupied
deactivated
no
remote
on
active
-
on_auto
remote
occupied
deactivated
no
remote
on
active
enabled
-
network
occupied
deactivated
no
network
on
9
When the unit is about to stop or when there is a request to stop the unit, the compressors are stopped as well. In case of
emergency stop all compressors are stopped at the same time.