4.2.4
Partial heat recovery
This option allows producing hot water through the heat recovery by desuperheating the gas leaving the compressor. This option
is available for the whole range.
The water cooled heat exchanger is installed on the charge line of the compressor of each circuit.
The control is configured in the factory for the partial heat Recovery option (see the section on Control configuration with the
desuperheater option).
The installer must protect the water cooled exchanger from the frost.
PHYSICAL PROPERTIES OF THE UNIT WITH PARTIAL HEAT RECOVERY BY MEANS OF DESUPERHEATERS
Description
NXC
044
048
056
064
072
084
096
104
122
142
164
Standard unit
459
467
496
521
505
541
841
853
878
939
1002
kg
Unit + High pressure single pump
option
500
509
538
563
547
583
908
919
949
1013
1076
kg
Unit + High pressure double pump
option
526
535
564
589
572
609
953
964
997
1050
1113
kg
Unit + High pressure single pump
+ Backup Tank Module option
896
905
934
959
943
979
1341
1352
1382
1446
1509
kg
Unit + High pressure double pump +
Backup Tank module option
922
931
960
985
968
1005
1386
1397
1430
1483
1546
kg
Refrigerant with copper coils / alumin-
ium fins
(1)
R410A
3.8
4.4
5
5
5.2
6.2
6.5
8
8.7
8.9
3.4
Circuit A
8
9
12.5
15
12.5
15
19
20
23
12.5
16
kg
Circuit B
-
-
-
-
-
-
-
-
-
12.5
16
kg
Air heat exchanger
Grooved copper pipe and aluminium fins
-
Desuperheaters on circuit A and B
Plate heat exchanger
-
Water volume
0.549 0.549 0.549 0.549 0.732
0.732 0.976 0.976 0.976 0.732
0.732
L
Water volume
-
-
-
-
-
-
-
-
-
0.732
0.732
L
Max operating pressure on water side
without hydronic module
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
kPa
Water connections
Male cylinder threaded gas connection
-
Connectors
1
1
1
1
1
1
1
1
1
1
1
inch-
es
External diameter
42
42
42
42
42
42
42
42
42
42
42
mm
(1) Indicative weights only.
Description
NXH
044
048
056
064
072
080
084
096
104
122
142
164
Standard unit
506
515
552
558
569
574
787
907
916
990
1068
1072
kg
Unit + High pressure single pump
option
548
557
594
600
611
616
854
974
983
1061
1142
1146
kg
Unit + High pressure double pump
option
574
583
620
626
637
642
899
1019
1028
1109
1179
1183
kg
Unit + high pressure single pump +
Backup Tank module option
944
952
990
995
1006
1011
1286
1406
1415
1493
1575
1578
kg
Unit + High pressure double pump +
Backup Tank module option
970
978
1015
1021
1032
1037
1331
1451
1460
1542
1612
1615
kg
Refrigerant with copper coils / alumin-
ium fins (1)
R410A
-
Circuit A
12.5
13.5
16.5
17.5
18
16.5
21.5
27.5
28.5
33
19
18.5
kg
Circuit B
-
-
-
-
-
-
-
-
-
-
19
18.5
kg
Air heat exchanger
Grooved copper pipe and aluminium fins
-
Desuperheaters on circuit A and B
Plate heat exchanger
-
Water volume
0.549 0.549 0.549 0.732 0.732 0.732 0.732 0.976 0.976 0.976 0.732 0.732
L
Water volume
-
-
-
-
-
-
-
-
-
-
0.732 0.732
L
Max operating pressure on water side
without hydronic module
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
kPa
Water connections
Male cylinder threaded gas connection
-
Connectors
1
1
1
1
1
1
1
1
1
1
1
1
inch-
es
External diameter
42
42
42
42
42
42
42
42
42
42
42
42
mm
(1) Indicative weights only.