41
INSTALLATION
2.15.2
Parameters' list
Parameters are listed base on the reference menu.
Reference Menu
M1
Parameters Menu
M2
Cascaded module configuration menu
M3
Cascaded boiler configuration menu
M4
Appliance configuration menu
Access type
U
End user
I
Installer
O
Manufacturer
Menu Par.
No.
Nr. dis-
played
Display
Description
Range
Default
setting
UM
Access
type
Category
M1
1
CH mode
Defines the thermal module's various heating
operation modes.
0…5
0
I
Heating
M1
3
CH set-
point
Defines the desired delivery temperature in heating
mode (Par. 1) = 0.
Par. 23…Par. 24
70
°C
U
Heating
M1
109
Calc.
set-point
off-set
Establishes the set-point offset value calculated in
climatic mode (Par. 1= 1). Offsets the climatic curve
in presence of mild outdoor temperatures.
Off, -10…10
0
I
Heating
M1
110
CH Min.
Set-
point
Sets the minimum delivery temperature value in
heating mode (Par. 1) = 4.
20…50
30
°C
I
Heating
M1
111
CH Min.
Set-
point
Sets the maximum delivery temperature value in
heating mode (Par. 1) = 4.
50…90
80
°C
I
Heating
M1
5
Boiler
Pump
Overrun
Sets the overrun time in seconds of the boiler's
circulator during stand-alone operation; cascaded
operation determines the module's overrun after
switch-off due to temperature control.
0…900
60
Sec.
I
Heating
M1
6
Flue
Temp.
Limit
Sets the activation temperature when the maxi-
mum flue gas temperature is exceeded. When the
flue gas temperature is higher than a set value,
the module switches off and an error message is
generated. When the flue gas temperature is in
the interval between (Par. 6) -5°C and Par. 6, the
module reduces its power in a linear way until it
reaches minimum power when the temperature
measured is equal to Par. 6.
10…120
100
°C
O
General
M1
7
CH Hys-
teresis
Sets the value in degrees beyond the set-point at
which the burner switches off for thermoregula-
tion.
0…20
5
°C
I
Heating
M1
112
CH Hys-
teresis
Down
Sets the value in degrees below the set-point at
which the burner switches on again for thermoreg-
ulation.
0…20
5
°C
I
Heating
M1
9
An-
ti-cycle
Period
Sets the stand-by time before the appliance is
switched on again after it switches off due to
thermoregulation, independently from the delivery
temperature dropping below the value indicated in
Par. 10. Parameter valid only in stand-alone mode.
10…900
120
Sec.
I
Heating
M1
10
Anti-cy-
cle Temp.
Diff.
Sets the value in degrees below which the burner
switches on again notwithstanding from the time
spent at Par. 9.
0…20
16
°C
I
Heating
M1
12
Hx diff.
Mini-
mum
Sets the value of the temperature difference (Delta
T) between the module's delivery and return tem-
perature. For a Delta T value ranging between Par.
12 and (Par. 12) +8°C, the module reduces its power
in a linear fashion until it reaches the minimum
power. The minimum power is maintained until
reaching (Par. 12) +8°C+5°C, after which the module
switches off for a period of time equal to the value
attributed to Par. 13; at the end of this time interval,
the module switches on again.
10…60
40
°C
O
General
M1
13
Hx Diff.
Max.
Wait
Time
Defines the restart time after reaching the Delta T
limit between delivery and return.
10…250
30
Sec.
O
General
M1
14
Max.
Power
CH
Sets the heating's % max. power.
50…100
100
%
I
Heating