INSTALLATION
Loosen the fixing screws (2) and remove the protection (3)
2
3
− Identify the low-tension terminal board (MO1) and the
high-tension terminal board (MO2)
MO1
MO2
FC
MO1
Control signals terminal board
MO2
Output terminal board
FC
Cable guide
9
For the connection of the devices connected to the jig
(pumps, circulators and diverting / mixing valves) use inter-
posed relays unless the maximum absorption of all compo-
nents connected to the board (including the module circu-
lator) is less than or equal to 1.5 A. Relays sizing lays on the
installer depending on the type of connected device.
For connection, see the following figure:
~ 230 V
1
S1
0
N
( )
RA
MO2
101 102 103 104 105 106 107 108 109 110 111 112 113 114 115
S1
Circuit breaker
RA
Relay / Switch (230V AC)
(*)
Refer to the device type for the supply tension.
− Execute electrical wiring in compliance with the diagrams
shown below
Power supply
230V ~ 50Hz
L
N
L
N
L
N
103 104 105 106 107 108 109 110 111 112 113 114 115
L
N
L
N
MO2
L
Live
N
Neutral
PE
Earth/ground
Electrical wiring referred to layout 1 at page "20".
MO1
BUS 1
SE
SB
SS
Modbus
0-10V
TA
1
2
3
4
9 10 11 12 13 14
5 6 7 8
TA
TA
TA
Room/heat demand thermostat
NOTE
The room thermostat connection must be dry (no
voltage).