60
COMMISSIONING AND MAINTENANCE
For all models
− Fulfil the operations, place back the front panel and lock
the locking screws.
− Open the gas detection valve.
− Switch the electricity supply ON at the system's main
switch and at the control panel.
− Make sure that there is no heat or DHW demand.
It is now necessary to change the setting of the parameter 98.
Proceed as follows:
− On the home screen of the control panel, press the
●
key
− Select "Settings" with the
▲
/
▼
keys and press the
●
key
− Select "Device configuration" with the
▲
/
▼
keys and
press the
●
key
“
Settings
”
“
General Settings
”
“
Boiler Settings
”
“
Appliance Configuration
”
− Enter the password as described in paragraph "Password
access"
− Press the
▼
key, select "(98) Type of Gas" and press the
●
key
“
Appliance Configuration
”
“
(97) IO Configuration
”
1
“
(98) Appliance Settings
”
2
“
Configuration Confirmed
”
“
No
”
− With the
▲
/
▼
keys change the value following what is in
the following table and press the
●
key:
Model
Parameter 98
Condexa PRO 35 P
22
Condexa PRO 50 P
20
Condexa PRO 57 P
12
Condexa PRO 70 P
10
Condexa PRO 90
8
Condexa PRO 100
6
Condexa PRO 115
4
Condexa PRO 135
2
− Press the
▼
key, select "Config. Confirmed" and press the
●
key
− With the
▲
/
▼
keys change the value to "Yes" and press
the
●
key
“
Appliance Configuration
”
“
(97) IO Configuration
”
1
“
(98) Appliance Settings
”
4
“
Configuration Confirmed
”
“
Yes
”
At this point the systems starts an application update process.
Once this is finished, the menu "Settings" appears on the menu.
− Press
◄
until you return to the home screen
An error message is displayed for a few seconds and then the
display returns to its normal state.
Remove the adhesive (valid for G20 supply) and use the one for
G30-G31.
Gruppo termico regolato per:
G30 - G31 28-30/37 mbar
Paese di destinazione:
Paese di destinazione:
Tipo di apparecchio
Caldaia categoria
:
:
B23
II
2H3+
Pressioni di alimentazione gas:
Regolazione effettuata dal costruttore:
G20 - 20 mbar - 2H METANO
ATTENZIONE
Leggere attentamente il libretto istruzioni
prima di installare e mettere in servizio
l'apparecchio.
(Laterale DX)
Temperatura ambiente:
min. -10°C max. 50°C
Questo apparecchio puó essere installato e
funzionare all'aperto o solo in locali
permanentemente ventilati secondo norma
UNI7129.
068411_E0
G20 20 mbar
G30 28-30 mbar
G31 37 mbar
After installing the accessory, check all gaskets tightness.
Carry out all calibration activities described in Paragraph "Ad-
justments".
Restore the desired set points.