11
GENERAL INFORMATION
Description
Condexa PRO
U.M.
35 P
50 P
57 P
70 P
90
100
115
135
Emissions (**)
NOx (referred
to HCV)
42,0
43,9
34,2
36,4
38,1
38,7
39,3
46,1
mg/
kWh
Emissions at max./min. heat input,
G20
CO
2
9 - 9
%
CO
63/2,3 73/2,3 79/6,5 90/6,5 81/7,5 91,5/7,5 89/4,6 91,5/5,6 ppm
Maximum rated heat input (LCV)
G25
34,9
45
53
65
85
93
107
127
kW
Minimum rated heat input (LCV)
G25
9
9
13
13
18,1
18,5
21,4
24,5
kW
Emissions at max./min. heat input,
G25
CO
2
9 - 9
%
CO
72/3,2 80/3,2
92/7
93,5/7
84/8
94/8
92/6
95/7
ppm
Emissions at max./min. power G30
CO
2
10,4-9,9
10,4-10,4
%
CO
132/6
137/6
138/10 142/10
148/11
159/11
172/13
180/15
ppm
Emissions at max./min. power G31
CO
2
10,4-9,9
10,4-10,4
%
CO
136/8
141/8
142/11
147/11
153/12
163/12
177/14
185/16
ppm
Flue gas temperature at max. power and min. power
80-60°C
66,5/61 67,5/61
71/61
72/61
76/62
78/62
75/61
77/61
°C
Flue gas temperature at max. power and min. power
50-30°C
44/32
45/32
45/33
46/33
47/35
49/35
45/33
48/35
°C
Flue gas mass flow rate (***)
0,015
0,02
0,025
0,03
0,04
0,046
0,05
0,06
Kg/s
Water-side resistance (
∆
T 20°C)
-
-
-
-
160
210
350
510
mbar
Available useful discharge head (
∆
T 20°C)
420
250
490
390
-
-
-
-
mbar
Maximum working pressure
6
bar
Minimum supply pressure
0,7
bar
Maximum permitted temperature
100
°C
Lockout thermostat activation temperature
95
°C
Adjustment temperature (min / max)
30 / 80 (****)
°C
Thermal module water content
5
5
15
15
17
17
23
25
l
Maximum condensation at 100% rated heat output
(50-30°C)
5,4
7,0
8,9
10,1
13,6
15,0
17,5
19,8
l/h
Power supply
230-50
V-Hz
Index of protection
IPX4D
IP
Consumption at full load
Elmax
75
105
63
77
150
203
205
302
W
Consumption at part load
Elmin
31
34
30
30
36
31
44
45
W
Electrical consumption in standby
mode
Psb
9
9
13
13
6
6
6
8
W
(**)
Weights calculated according to EN 15502.
(***)
Values referred to atmospheric pressure at sea level.
(****)
Up to 85°C if combined with the plate heat exchanger accessory.