=>  Photocell 2 (NC) contact

10 

=>  Pedestrian opening command (NO)

11 

=>  Free contact

12 

=>  Common unit 

EXPANDER 12V 

CARD LED SIGNALS

D2

Photocell 2 contact signal

D3

Pedestrian contact signal

D4

Free

D5

Voltage presence

N.B.: LED D2 and LED D5 must always be turned on for a correct functioning.

PEDESTRIAN OPENING BUTTON (10-12)

This command operates the partial opening of the gate and its closing. When the gate Is
partly open, It Is not possible to operate Its total opening using the pedestrian command. 
It is possible to close the gate again to open it totally.
It  enables  exclusively  the  pedestrian  opening  and  closing,  following  the  jogging  mode
(open-stop-close-stop-etc...).

LEARNING PROCEDURE FOR THE PEDESTRIAN OPENING

1 - 

First, position DIP2 on mode ON 

(the LED DL5 blinks quickly) 

and then DIP1 on

mode ON

(the LED DL5 blinks slowly). 

2 - Push the pedestrian button => The sliding gate opens.
3 - Push the pedestrian button to stop the gate travel, thereby determining its opening.
4 - Wait as long as you want the gate to remain open  (excluded by 

DIP9 on OFF

), than

push the pedestrian button to operate the closing cycle.

5 - When the closing limit switches are reached, position DIP1 and 2 back on mode OFF.
Safety devices are ready to operate during the programming and their action stops it (the
LED does not blink anymore but remains turned on).
To  repeat  the  programming,  position  DIP1  and  2  on  mode  OFF,  close  the  gate  and
repeat the procedure described above.

AUTOMATIC PEDESTRIAN CLOSING

Pause  times  before  the  automatic  pedestrian  closing  are  set  with  the  programming
procedure.
The max. pause time Is 5 minutes.
You can start and stop the pause time using DIP9 (ON started).

PHOTOCELL 2 (9-12)

If it detects an object during the opening cycle, it then operates the closing of the gate at
the end of the interposition. If it detects one during the closing cycle, it then operates the
opening at the end of the interposition.
This function is particularly helpful when you want the gate to close immediately after you
passed it. 

If it is not used, jumper the terminals 9-12.

COURTESY LIGHT (7-8)

It is possible to supply 12Vdc power to the coil of a relay, so as to feed one lamp or more
for a minimum period of 1 second and for a maximum period of 4 minutes (controlled by
the TR trimmer fitted on the EXPANDER card).
The relay is activated at every opening or closing.

TRAFFIC LIGHT CONTROL

When the gate is closed, the traffic light is turned off. 

The red light (3-4)

turns on when the gate opens.

The green light (5-6)

turns on when the gate Is open and the red light turns off.

The green light remains turned on until the automatic closing starts.
When the gate closes, the green light turns off and the red light turns on.
When the closing is terminated, the traffic light turns off.

BATTERY CHARGE CARD

Code ACG4646 for K400
The 12Vdc 7 Ah battery recharge time (optional code ACG9510), at the first installation is 24
hours, with 0,03 current supplied.

WARNING LIGHT FOR THE BATTERY STATE

In  case  of  network  voltage  drop,  with  safety  battery  activation,  this  warning  light  turns  on,
signalling the power mains failure, and starts blinking only when the battery is charged. 
When the warning light blinks, all functions of the control board are inhibited.
The  warning  light  turns  off  only  when  the  network  is  supplied  with  the  due  voltage  and  all
commands are ready to work again (the battery recharges only when the network voltage is
available).

NB: If you use too many warning lights, you risk to compromise the logic of the control
unit, possibly causing an operation block.

OPERATION WITH BLACK OUT

If a battery Is connected to the control board, the warning light indicating the battery state turns
on when the voltage is not enough, and signals that the system is operating with the battery.
Gate operation is guaranteed up to a charge level of about 10V. Beyond this level, the charge
card gives a signal to the microprocessor that stops the gate, making blink the warning light -
gate open - and the warning light - battery state -. Once the network voltage is available again,
the recharge card starts recharging the battery.
You just need to press the remote control (the opening button or the jogging operation button)
to open the gate. When the gate Is open, operate a closing command or wait until the pause
time  elapses  and  the  gate  automatically  closes.  The  gate  starts  from  the  closing  position.
When It Is closed, every normal function Is ready to be activated again.
If  no  battery  is  connected  to  the  control  board,  you  do  not  need  to  follow  any  particular
procedure.  When  the  network  voltage  Is  available  again,  just  press  the  remote  control,  the
opening  button  or  the  button  for  the  jogging  operation,  in  order  to  open  the  gate.  When  the
gate Is open, operate a closing command or wait until the pause time elapses and the gate
automatically closes. The gate starts from the closing position.
When the gate is closed, every normal function is ready to be activated again.
Safety devices are ready to operate during the alignment phase.

RADIO TRANSMITTER MOON

MOON 91 (30,925MHz) - 2CH Code ACG7025 - 4CH TX91 Code ACG7026

*

Ref. Min. Certificate P.T. of EC inspection n. EMC/98/IST/012 

*

Min. Authorization  P.T. DGPGF/SEGR/2/07/336915/FO  

*

EC CERTIFICATE OF COMPLIANCE OF THE KIND 

*

CERTIFICATE OF CONFORMITY (GERMANY) 

*

CERTIFICATE EXPERT OPINION (GERMANY) 

*

MOON 433 (433,92MHz) - 2CH Code ACG6081 - 4CH Code ACG6082

*

Ref. Min. Certificate P.T. of EC inspection n. EMC/97/084 

*Min. Authorization P.T. CEPT LPD-I DGPGF/4/2/03/338529/FO/  
*EC CERTIFICATE OF COMPLIANCE OF THE KIND 
*

CERTIFICATE OF CONFORMITY (GERMANY) 

*

CERTIFICATE EXPERT OPINION (GERMANY)

RADIO RECEIVERS

RX91/A

with code learning system and coupling

code ACG5005

RX91/A

with code learning system and terminal board 

code ACG5004

RX433/A

with code learning system and coupling

code ACG5055

RX433/A

with code learning system and terminal board 

code ACG5056

RX433/A 2CH 

with code learning system and coupling 

code ACG5051

RX433/A 2CH 

with code learning system and terminal board

code ACG5052

Pag. 19 di 28

E

N

G

L

I

S

H

D5
D4
D3
D2

ACG6081 - 433
ACG7025 - 91

ACG6082 - 433

ACG7026 - 91

Summary of Contents for AA20016

Page 1: ...stallazione regolazione manutenzione dell impianto togliere la tensione agendo sull apposito interruttore magnetotermico collegato a monte dello stesso ATTENZIONE UNA SCORRETTA INSTALLAZIONE PU PORTAR...

Page 2: ...ting Maintenance pag 16 Connections pag 16 Electronic board KS 12V Connections pag 17 Operating micro switches Led signals pag 17 Checking the rotation direction of the motor Timing pag 18 Operation o...

Page 3: ...resente A B a impulsi in vista es sensore C C C e D a impulsi non in vista es telecomando C C e D C e D automatico C e D C e D C e D esempio tipico sono le chiusure che non accedono a pubblica via A P...

Page 4: ...ispetto alla cremagliera 3 FISSAGGIO FINECORSA Per determinare la corsa della parte mobile si devono posizionare due camme alle estremit della cremagliera Fig 7 La regolazione della corsa di apertura...

Page 5: ...golo K BUTT passo passo OFF automatico ON DIP 6 Fotocellule sempre attive OFF Fotocellule attive solo in chiusura ON DIP 7 Encoder per modello PLUS ON attivato DIP 8 Prelampeggio ON Lampeggio normale...

Page 6: ...der abilitato dal DIP 7 ON In caso di mancato funzionamento dell Encoder non alimentato fili staccati disco rotto o difettoso la movimentazione del cancello non viene eseguita Se dopo l intervento del...

Page 7: ...ACG9510 alla prima installazione di 24 ore con una corrente di carica di 0 03 A ALIMENTAZIONE SPIA DI SEGNALAZIONE STATO BATTERIA In caso di mancanza di tensione di rete con intervento della batteria...

Page 8: ...DA INCASSO cod ACG1048 ANTENNAANTENNA SPARK Per ottenere le migliori prestazioni degli apparati sopracitati bisogna installare un antenna accordata sulla frequenza del radio ricevitore installato N B...

Page 9: ...C C e D impulsion hors de vue bo tier de commande C C e D C e D automatique C e D C e D C e D example typique fermetures qui n ont pas d acc s un chemin public A Touche de commande homme present acti...

Page 10: ...miner la course de la partie mobile il faut positionner deux cames sur les extr mit s de la cr maill re Fig 7 Pour proc der au r glage de la course d ouverture et de fermeture il suffit de d placer le...

Page 11: ...nt lors de la fermeture ON DIP 7 Encodeur pour mod le PLUS ON actionn DIP 8 Pr clignotement ON Clignotement normal OFF DIP 9 Activation fermeture automatique pi tonne ON avec EXPANDER DIP 10 LIBRE SIG...

Page 12: ...l ouverture que lors de la fermeture avec inversion du mouvement Le fonctionnement du moteur avec encodeur est actionn travers le DIP 7 ON En cas de non fonctionnement de l encodeur manque d alimentat...

Page 13: ...alisation s teint CARTE DE CHARGE BATTERIE Cod ACG4646 pour K400 Lors de la premi re installation le temps de recharge compl te de la batterie de 12Vdc 7 Ah option cod ACG9510 est de 24 heures avec un...

Page 14: ...CL ENCASTRER code ACG1048 ANTENNE SPARK Afin d optimaliser les performances des appareils suscit s il est indispensable d installer une antenne accord e sur la fr quence du radior cepteur install N B...

Page 15: ...n A B with visible impulses e g sensor C C C e D with not visible impulses e g remote control device C C e D C e D automatic C e D C e D C e D a typical example are those shutters which do not have ac...

Page 16: ...k 3 LIMIT SWITCH FITTING In order to determine the travel of the moving part place two cams at the ends of the rack Fig 7 Move the cams on the rack teeth to adjust their opening and closing travel To...

Page 17: ...g OFF automatic ON DIP 6 Photocells always active OFF Photocells only when the gate closes ON DIP 7 Encode for the PLUS model ON started DIP 8 Pre blinking ON Normal blinking OFF DIP 9 Pedestrian auto...

Page 18: ...coder If the Encoder does not work due to power supply failure disconnected wires broken or defective disk the gate Is not operated If the encoder operates the opening or the closing and than gives a...

Page 19: ...HT FOR THE BATTERY STATE In case of network voltage drop with safety battery activation this warning light turns on signalling the power mains failure and starts blinking only when the battery is char...

Page 20: ...ON code ACG1053 BLOCK KEY SELECTOR TO BUILD IN code ACG1048 SPARK ANTENNA In order to make the systems mentioned above give the best performances you need to install an antenna tuned on the frequency...

Page 21: ...Sensor C C C e D mit nicht sichtbaren Impulsen z B Fernsender C C e D C e D automatisch C e D C e D C e D ein Musterbeispiel daf r sind jene T re die keine Zufahrt zu einem ffentlichen Weg haben A Be...

Page 22: ...RS Um den Lauf des mobilen Teils zu beenden m ssen zwei Nocken an den Enden der Zahnstange positioniert werden Abb 7 Die Regulierung des ffnungs und Schlie laufes wird erhalten indem diese entlang der...

Page 23: ...mmer aktiv OFF Fotozellen nur beim Schlie en aktiv ON DIP 7 Encoder f r Modell PLUS ON aktiviert DIP 8 Vorblinken ON Normales Blinken OFF DIP 9 Aktivierung automatisches Schlie en Personen ffnung ON m...

Page 24: ...itsvorrichtung sowohl in der ffnungs als auch in der Schlie phase zu wirken Der Betrieb des Motors mit Encoder wird mit dem DIP7 ON aktiviert Falls der Encoder Betrieb nicht funktioniert keine Stromve...

Page 25: ...wird die Ampel abgeschaltet BATTERIELADEKARTE Kennr ACG4646 f r K400 Die vollst ndige Ladezeit der Batterie mit 12 Vdc 7Ah optional Kennnr ACG9510 betr gt bei einem Ladestrom von 0 03 A bei der Erstin...

Page 26: ...ACG3010 Mit doppeltem Sicherheitskontakt Abmessungen k nnen nach Wunsch geschnitten werden SCHL SSELWAHLSCHALTER BLOCK F R DIE WAND ACG1053 SCHL SSELWAHLSCHALTER BLOCK ZUM EINBAU ACG1048 ANTENNE Um d...

Page 27: ...e up of various other elements Hence it falls within Article 4 Paragraph 2 of the EC Directive 89 392 Machines and following modifications to which respect we point out the ban on its putting into ser...

Page 28: ...ice Denominazione Particolare CME2082 CME3066 CMO2600 CPL1174 CPL1175 CPL1176 CPL1177 CPL1178 CPL1179 CPL1217 CPL1218 CPL1219 CPL1220 CPL1221 CPL1226 CTC1012 CTC1018 Perno di sblocco Flangia anteriore...

Reviews: