11.2 Warning Code
Panel
display
Description
Cause
Countermeasures
Fdi
Fieldbus proc-
ess data inva-
lid
●
Cyclic communication had
been established, but was stop-
ped because of an error.
●
Cyclic communication is run-
ning, but fieldbus master has
set data status invalid.
●
Check fieldbus master status, if the
controller is in stop mode Fdi warn-
ing will appear also.
●
Check Ethernet cable and switches.
●
At the PLC, set application status
and/or process data status valid.
Tab. 11-4: Warning code
Bosch Rexroth AG
Diagnosis
Multi-Ethernet Card
56/61
DOK-RCON0*-XFCX610*MUL-IT02-EN-P