11 Diagnosis
11.1 LED Indications
The Network Status LED (Hx1) expresses the status of the MEP and the field-
bus:
Network status LED
Meaning
PROFINET IO, EtherNet/IP and Modbus/TCP
Continuous off
Multi-Ethernet card
●
does not have a valid IP address
●
has not seen an Ethernet link
●
powered off
●
an MEP firmware update process was running
Blinking green
Does have a valid IP address, but no cyclic connection was established
Continuous green
Cyclic connection is established and it is free of errors
Blinking red
Cyclic connection was terminated unexpectedly
Continuous red
Duplicate IP address in network detected
Blinking green/red
Multi-Ethernet card is in power up mode and is conducting a self-test
SERCOS III
Continuous off
NRT state (no SERCOS III communication)
Continuous orange
Communication phase 0
Orange with 1 green pulse
Communication phase 1
Orange with 2 green pulses
Communication phase 2
Orange with 3 green pulses
Communication phase 3
Continuous green
Communication phase 4
Blinking green/orange
Hotplug phase 0
Green with 1 orange pulse
Hotplug phase 1
Green with 2 orange pulses
Hotplug phase 2
Blinking green
Switched from Fast-Forward to Loopback
(e.g. due to link loss at one port)
Blinking red/orange
Application error
Blinking green/red
Warning for MST losses exceeded half of tolerable losses
Continuous red
Communication error
Blinking orange
Identification
Blinking red
Firmware watchdog error
EtherCAT
Off
Status Init
Bosch Rexroth AG
Diagnosis
Multi-Ethernet Card
54/61
DOK-RCON0*-XFCX610*MUL-IT02-EN-P
Summary of Contents for efc series
Page 1: ...Frequency Converter Multi Ethernet Card Instruction Manual R912006860 Edition 02 ...
Page 6: ...Bosch Rexroth AG Multi Ethernet Card IV DOK RCON0 XFCX610 MUL IT02 EN P ...
Page 65: ...Multi Ethernet Card Bosch Rexroth AG DOK RCON0 XFCX610 MUL IT02 EN P 59 61 ...
Page 66: ...Bosch Rexroth AG Multi Ethernet Card 60 61 DOK RCON0 XFCX610 MUL IT02 EN P ...