![REXROTH efc series Instruction Manual Download Page 18](http://html1.mh-extra.com/html/rexroth/efc-series/efc-series_instruction-manual_1449615018.webp)
4.4 Device Profile
The Rexroth device profile described below is used as common profile for the
MEP extension card.
The following table is a general description of the H0.00 control words which
are used to send commands from master to slave.
Bit
Value
Meaning
15…9
-
Reserved
8
1
Freewheeling stop
0
Inactive
7
1
Control word active
0
Inactive
6
1
Stop Acc. / Dec. active (stop the internal Acc. / Dec. ramp generator)
0
Inactive
5
1
Fault reset active
0
Inactive
4
1
E-stop active
0
Inactive
3
1
Stop according to parameter setting
0
Inactive
2
1
Reverse
0
Forward
1
1
Jog active (jogging direction determined by bit 2)
0
Inactive
0
1
Run command active
0
Inactive
Tab. 4-7: Control word definition
●
Bit 8 Freewheeling stop
Freewheeling stops that ignore the frequency converter stop mode setting. Only
active start from frequency converter firmware version 03V12.
●
Bit 6 Stop acceleration/deceleration active
The current acceleration/deceleration process will be paused when bit 6 = 1,
and it will be recovered when bit 6 = 0.
●
Bit 4 E-stop active
Freewheel stop will be triggered in conjunction with panel display error ‘E-St’
when bit 4 = 1.
●
Bit 3 Stop according to parameter setting
The parameter E0.50 Stop Mode is referenced when bit 3 = 1.
Bosch Rexroth AG
General Configuration
Multi-Ethernet Card
12/61
DOK-RCON0*-XFCX610*MUL-IT02-EN-P
Summary of Contents for efc series
Page 1: ...Frequency Converter Multi Ethernet Card Instruction Manual R912006860 Edition 02 ...
Page 6: ...Bosch Rexroth AG Multi Ethernet Card IV DOK RCON0 XFCX610 MUL IT02 EN P ...
Page 65: ...Multi Ethernet Card Bosch Rexroth AG DOK RCON0 XFCX610 MUL IT02 EN P 59 61 ...