E
B
B
A D
C
11
1
5
5
8
1
9
3
Fig. 25: Dimensions for the strip foundation
MVV 1200-1600 DC (bird's eye view)
For the designations of 1,3,5,8,9 and 11, please
refer to the legend for the Fig. 24
5
E
B
B
A D
C
11
1
5
5
8
1
9
3
F
B
Fig. 26: Dimensions for the strip foundation
MVV 2000 DC (bird's eye view)
For the designations of 1,3,5,8,9 and 11, please
refer to the legend for the Fig. 24
Dimensioning of the strip foundation (all meas-
urements in mm)
Dimen-
sion
MVV 1200-1600
DC
MVV 2000 DC
A
800
800
W
200
200
C
600
665
D
365
495
E
400
465
F
-
205
Condensate drainage connection
If the temperature falls below the dew point, con-
densation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the
underside of the unit to drain any condensate.
n
The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer. If necessary, fit vapour-diffusion-
proof insulation.
n
When operating the unit at outdoor tempera-
tures below 4
℃
, care must be taken that the
condensate drainage line is anti-freeze pro-
tected. The lower part of the housing and con-
densate tray is also to be kept frost free in
order to ensure permanent draining of the con-
densate. If necessary, fit a pipe heater.
n
Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the fol-
lowing list of requirements from regional regula-
tions and laws.
NOTICE!
Local regulations or environmental laws, for
example the German Water Resource Law
(WHG), can require suitable precautions to
protect against uncontrolled draining in case of
leakage to provide for safe disposal of
escaping refrigerator oil or hazardous media.
NOTICE!
If condensate is removed via a duct in accord-
ance with DIN EN 1717, ensure that any micro-
biological contamination present on the waste-
water side (bacteria, fungi, viruses) cannot
enter the unit connected to it.