NOTICE!
When configuring and topping up the system
with refrigerant, observe the practical limit
value for refrigerants according to DIN EN
378-1! Practical limit value R410A: 0.44 kg/m
3
room volume of the smallest room. If this is
exceeded, implement suitable measures for
reducing the possible refrigerant concentration
per DIN EN 378-1.
Example:
The calculation of the refrigerant quantity to be
added provides the following:
Refrigerant quantity to be added: 4.11 kg
Basic fill quantity of the outdoor unit: 3.9 kg
Total fill quantity: 8.01 kg
Practical limit value R410A: 0.44 kg/m
3
8.01 kg / (0.44 kg/m
3
) = 18.20 m
3
This equates to a min. room size of the smallest air
conditioned room of approx. 2.7 x 2.7 x 2.5 m.