3.2 Combinations
The indoor units from the series MVD and MVW can be used together with the MVV series outdoor units.
Selection of the indoor units to be connected takes place solely according to the maximum refrigerating
capacity of all indoor units to be connected. Max. 130%.
The power factor takes into account the fact that all indoor units are never required to deliver 100% capacity
at the same time.
The design of the system and the inclusion of the power factor must always take place with consideration to
the local conditions!
Outdoor unit
Type
Power
Power factor
Maximum refrigerating capacity of the indoor
units to be connected
MVV 1200 DC
12.0 kW
130 %
15.6 kW
MVV 1600 DC
15.5 kW
130 %
20.2 kW
MVV 2000 DC
20.0 kW
130 %
26.0 kW
MVV 1200 DC Duo
2x12.0 KW
130 %
2 x 15.6 kW
MVV 1600 DC Duo
2x15.5 kW
130 %
2 x 20.2 kW
MVV 2000 DC Duo
2x20.0 kW
130 %
2 x 26.0 kW
In the following you will find example installations for the MVV series with the indoor units from the MVD
series and MVW
A
B
2
1
3
4
Fig. 11: connection possibilities on one level
A: Outdoor area
B: Indoor area
1: Outdoor unit
2: Indoor units of the series MVD or MVW
3: Distributor
4: Y-distributor