The following sketch and the empty table are provided for calculating the refrigerant quantity to be added
and must be completed by the installer.
Fig. 23: Sketch for determining the refrigerant quantity to be added
Component
Number
Fill factor
Additional fill
quantity
Length of the liquid pipe 1/4"
m
0.023 kg/m
kg
Length of the liquid pipe 3/8"
m
0.060 kg/m
kg
Number of distribution units in the liquid pipe
0.1 kg/unit
kg
Number of Y-pieces in the liquid pipe
0.1 kg/unit
kg
Sum
kg
29