Error code E5: Voltage monitoring has tripped
Is the power supply to the outdoor unit 220 –
230 Volt?
NO
Ensure the correct power supply
YES
Replace power pcb. Is the fault still present?
YES
Replace the control board
Error code E6: Fan motor fault
Is the fan motor correctly mounted on the
board?
NO
Correctly mount the fan motor on the board
YES
Can the shaft of the fan motor be rotated
easily?
NO
Replace fan motor
YES
Is the output voltage of the board between the
black and white contacts of the fan motor 15
Volt when in standby operation?
NO
Replace the control board
YES
Is the output voltage of the board between the
black and yellow contacts of the fan motor over
2.4 Volt?
NO
Replace the control board
YES
Replace fan motor
REMKO MVV...DC
50
Summary of Contents for MVV 1200 Dc
Page 67: ......