5. With the key select the desired language.
6. Press the
key to confirm the selection.
RESET ALL will be displayed.
7. To confirm, press the
key.
8. The selected language is now set-up and the main display will appear.
9. Set the components (thermostats, control) so that heat is demanded.
Important
In the event of an error during the start-up, a message with the
corresponding code is displayed. The meaning of the error codes
can be found in the error table.
For more information, see
7.6
Gas settings
7.6.1
Adjusting to a different gas type
Warning
Only a qualified engineer may carry out the following operations.
The factory setting of the boiler is for operation with the natural gas group
G20 (H gas).
Tab.25 Factory settings G20 (H-gas)
Code
Description
Range
160
DP003
Maximum fan speed on Domestic Hot Water
1000 Rpm - 7000 Rpm
6700
GP007
Maximum fan speed during Central Heating mode
1000 Rpm - 8500 Rpm
6700
GP008
Minimum fan speed during Central H
Domestic Hot Water mode
900 Rpm - 8500 Rpm
1900
GP009
Fan speed at appliance start
900 Rpm - 5000 Rpm
2200
Before operating with a different type of gas, carry out the following steps:
1. Fit the gas diaphragm in the gas block. If the boiler is modified, for
G30/G31 (butane/propane) :
Tab.26 Gas diaphragm for G30/G31 (butane/propane)
Gas diaphragm for G30/G31 (butane/propane)
Ø (mm)
Quinta Ace 160
9.0
Fig.40
Step 5
AD-4100149-01
Fig.41
Step 6
AD-4100150-01
Fig.42
Step 7
AD-4100148-01
Fig.43
Installing gas diaphragm
AD-3000835-01
7 Commissioning