11. Press the
h
key multiple times to go back to the main display.
9.2
List of parameters
The code of the parameters always contain two letters and three numbers.
The letters stand for:
AP
Appliance related parameters
CP
Zone related parameters
DP
Domestic hot water related parameters
EP
Smart Solutions related parameters
GP
Gas-fired heat engine related parameters
PP
Central heating related parameters
Important
All possible options are indicated in the adjustment range. The
display of the boiler only shows the relevant settings for the
appliance.
For more information, see
Changing the parameters, page 49
9.2.1
Parameters - FSB-WHB-HE-150-300
Important
All tables show the factory setting for the parameters.
The tables also list parameters that are only applicable if the
boiler is combined with other equipment such as an outdoor
sensor.
All possible options are indicated in the adjustment range. The
display of the boiler only shows the relevant settings for the
appliance.
Tab.34
> FSB-WHB-HE-150-300 - Factory settings at user level
Code
Description
Range
160
AP016
Enable central heating heat demand processing
0 = Off
1 = On
1
AP017
Enable domestic hot water heat demand processing 0 = Off
1 = On
1
CP080
Room setpoint temperature of the user zone activity
5 °C - 30 °C
16
CP081
Room setpoint temperature of the user zone activity
5 °C - 30 °C
20
CP082
Room setpoint temperature of the user zone activity
5 °C - 30 °C
6
CP083
Room setpoint temperature of the user zone activity
5 °C - 30 °C
21
CP084
Room setpoint temperature of the user zone activity
5 °C - 30 °C
22
CP085
Room setpoint temperature of the user zone activity
5 °C - 30 °C
20
CP200
Manually setting the room temperature setpoint of
the zone
5 °C - 30 °C
20
CP320
Operating mode of the zone
0 = Scheduling
1 = Manual
2 = Antifrost
3 = Temporary
1
CP510
Temporary room setpoint per zone
5 °C - 50 °C
20
CP550
Fire Place mode is active
0 = Off
1 = On
0
Fig.68
Step 11
MW-3000316-01
9 Settings
50
7625116 - v.06 - 17102018