Tab.28 Checking/setting values for O
2
/CO
2
at full load for G20 (H
gas)
Values at full load for G20 (H gas)
O
2
(%)
CO
2
(%)
Quinta Ace 160
4.8 - 5.2
- 9.0
(1) Nominal value
Tab.29 Checking/setting values for O
2
/CO
2
at full load for G30/G31
(butane/propane)
Values at full load for G30/G31 (butane/
propane)
O
2
(%)
CO
2
(%)
Quinta Ace 160
5.1 - 5.4
- 10.4
(1) Nominal value
Caution
The O
2
values at full load must be lower than the O
2
values at
low load.
The CO
2
values at full load must be higher than the CO
2
values
at low load.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
4. Using the adjusting screw A, set the percentage of O
2
/CO
2
for the gas
type being used to the nominal value. This should always be inside
the highest and lowest setting limit.
Enable part load
1. Press the two keys on the left simultaneously to select chimney sweep
mode.
The device is now running at part load. Wait until L:XX° appears on
the display.
2. Press the
h
key to go back to the main display.
Checking/setting values for O
2
/CO
2
at part load
1. Measure the percentage of O
2
/CO
2
in the flue gases at part load.
2. Compare the measured value with the checking values in the table.
Tab.30 Checking/setting values for O
2
/CO
2
at part load for G20 (H
gas)
Values at part load for G20 (H gas)
O
2
(%)
CO
2
(%)
Quinta Ace 160
5.2
- 5.6
8.6 - 8.8
(1) Nominal value
Fig.47
Position of adjusting screw A
AD-0000139-02
2
1
A
Fig.48
Step 1
MW-3000325-01
7 Commissioning