6.5.3
Dimensions of flue gas outlet pipe
Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
d
1
External dimensions of flue gas outlet pipe
D
1
External dimensions of air supply pipe
L
1
Length difference between flue gas outlet pipe and air supply pipe
Tab.17 Dimensions of pipe
d
1
(min-max)
D
1
(min-max)
L
1
100/150 mm 99.3 - 100.3 mm
149 - 151 mm
0 - 15 mm
(1) Shorten the inner pipe if the length difference is too great.
6.5.4
Length of the air and flue gas pipes
Important
When using bends, the maximum chimney length (L) must be
shortened according to the reduction table.
The boiler is also suitable for longer chimney lengths and
diameters other than those specified in the tables. Contact us
for more information.
Room-ventilated model (B
23P
)
L Length of the flue gas outlet channel to roof feed-through
Connecting the flue gas outlet
Connecting the air supply
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler
obtains the necessary combustion air directly from the installation area.
Use adapters when using air supply and flue gas outlet pipes with
diameters other than 150 mm.
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
If the boiler is operated in a dusty environment (e.g. during the
construction phase), use of an air inlet filter is necessary.
Tab.18 Maximum chimney length (L)
Diameter
90 mm
100 mm 110 mm 130 mm 150 mm
Quinta Ace 160
5 m
8 m
15 m
37 m
(1) With retention of the maximum flue length it is possible to apply an extra 5
times 90º or 10 times 45º elbows.
Fig.17
Dimensions of concentric
connection
AD-3000962-01
ød
1
L
1
øD
1
Fig.18
Room-ventilated version
AD-0000220-01
L =
6 Installation
7625116 - v.06 - 17102018
31